Permit Number: T07CM00220
Parcel: 12108001B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM00220
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2007 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/05/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) GENERAL STRUCTURAL NOTES AND DETAILS REQUIRE MINIMUM FONT SIZE OF 1/8".

2) OCCUPANCY HAS BEEN DECLARED AS AN "M". THIS IS A FOOD PROCESSING FACILITY THEREFORE "F1" SHOULD BE PROPER OCCUPANCY.

3) CODE ANALYSIS FORM INDICATES SEPARATED USE. JUSTIFY "EXISTING" DEMISING WALL NOTATION. INDICATE REQUIRED SEPARATION PER TABLE 302.3.2 AND HOW DEMISING WALL COMPLIES WITH SECTION 706 OF THE IBC.
02/06/2007 GERRY KOZIOL WWM REVIEW Approved
02/07/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. The specified service sink is floor mounted and cannot be connected to the specified grease trap because the required flow control must be installed in a location that is readily accessible and visible. Reference Section 1014.3, UPC 2003.
3. Provide a vented flow control device for the 3-compartment sink. Reference Section 1014.3, UPC 2003.
4. Provide fixture descriptions for the floor sinks. Reference Section 401.1, UPC 2003.
5. Clarify the description of the hand sinks. Sheet P1 indicates a different type of sink than sheets FS-2 and E1. Reference Section 103.2.3, UPC 2003.
6. Complete the water isometric to show all of the pipe sizes. Reference Section 103.2.3, UPC 2003.
7. Complete the waste and vent isometric to show all of the pipe sizes. Reference Section 103.2.3, UPC 2003.
8. The 2-way cleanout shown in the waste and vent diagram is in violation of Section 707.6, UPC 2003.
9. Any fitting or connection in a drainage system that results in a reduction of the pipe area is prohibited (e.g. a 3" floor sink and a 2" waste line). Reference Section 316.4.1, UPC 2003.
10. Provide a floor drain in the kitchen. Reference Section 412.2, UPC 2003.
02/07/2007 ROBERT SHERRY WATER REVIEW Approved
02/07/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied Provide full fault calculations, starting with the terminals of the TEP transformer to the SES, than from the SES to the replaced panel.
02/07/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. Provide manufacturer's equipment data along with installed weights and the refrigerant information for the condensing units and evaporators for the walk-in freezer and walk-in refrigerator. Reference Section 301.6, IMC 2003.
3. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the condensing units. Reference Section 302.1, IMC 2003.
4. Show the size, routing, and termination of the condensate drains for the evaporators for the walk-in freezer and walk-in refrigerator. Reference Section 307.2, IMC 2003 and Section 807.2, UPC 2003.
5. Provide calculations demonstrating adequate ventilation for the F-1 occupancy. Reference Section 401.2, IMC 2003.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/16/2007 CINDY AGUILAR OUT TO CUSTOMER Completed
02/16/2007 SUE REEVES REJECT SHELF Completed