Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM00220
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/26/2007 | BETSY COTTLE | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
02/05/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1) GENERAL STRUCTURAL NOTES AND DETAILS REQUIRE MINIMUM FONT SIZE OF 1/8". 2) OCCUPANCY HAS BEEN DECLARED AS AN "M". THIS IS A FOOD PROCESSING FACILITY THEREFORE "F1" SHOULD BE PROPER OCCUPANCY. 3) CODE ANALYSIS FORM INDICATES SEPARATED USE. JUSTIFY "EXISTING" DEMISING WALL NOTATION. INDICATE REQUIRED SEPARATION PER TABLE 302.3.2 AND HOW DEMISING WALL COMPLIES WITH SECTION 706 OF THE IBC. |
02/06/2007 | GERRY KOZIOL | WWM | REVIEW | Approved | |
02/07/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. The specified service sink is floor mounted and cannot be connected to the specified grease trap because the required flow control must be installed in a location that is readily accessible and visible. Reference Section 1014.3, UPC 2003. 3. Provide a vented flow control device for the 3-compartment sink. Reference Section 1014.3, UPC 2003. 4. Provide fixture descriptions for the floor sinks. Reference Section 401.1, UPC 2003. 5. Clarify the description of the hand sinks. Sheet P1 indicates a different type of sink than sheets FS-2 and E1. Reference Section 103.2.3, UPC 2003. 6. Complete the water isometric to show all of the pipe sizes. Reference Section 103.2.3, UPC 2003. 7. Complete the waste and vent isometric to show all of the pipe sizes. Reference Section 103.2.3, UPC 2003. 8. The 2-way cleanout shown in the waste and vent diagram is in violation of Section 707.6, UPC 2003. 9. Any fitting or connection in a drainage system that results in a reduction of the pipe area is prohibited (e.g. a 3" floor sink and a 2" waste line). Reference Section 316.4.1, UPC 2003. 10. Provide a floor drain in the kitchen. Reference Section 412.2, UPC 2003. |
02/07/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
02/07/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Provide full fault calculations, starting with the terminals of the TEP transformer to the SES, than from the SES to the replaced panel. |
02/07/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. Provide manufacturer's equipment data along with installed weights and the refrigerant information for the condensing units and evaporators for the walk-in freezer and walk-in refrigerator. Reference Section 301.6, IMC 2003. 3. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the condensing units. Reference Section 302.1, IMC 2003. 4. Show the size, routing, and termination of the condensate drains for the evaporators for the walk-in freezer and walk-in refrigerator. Reference Section 307.2, IMC 2003 and Section 807.2, UPC 2003. 5. Provide calculations demonstrating adequate ventilation for the F-1 occupancy. Reference Section 401.2, IMC 2003. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/16/2007 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
02/16/2007 | SUE REEVES | REJECT SHELF | Completed |