Permit Number: T07CM00220
Parcel: 12108001B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM00220
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2007 STEVE SHIELDS ZONING REVIEW Approved
01/19/2007 FSANCHE1 MECHANICAL-COMMERCIAL REVIEW Needs Review
01/19/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied Provide full fault calculations, starting with the terminals of the TEP transformer to the SES, than from the SES to the replaced panel.
01/19/2007 FSANCHE1 WATER REVIEW Needs Review
01/19/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Needs Review
01/19/2007 FSANCHE1 WWM REVIEW Needs Review
01/19/2007 FSANCHE1 PLUMBING-COMMERCIAL REVIEW Needs Review
01/19/2007 SUZANNE BOHNET ENGINEERING REVIEW Approved
01/19/2007 MARTIN BROWN FIRE REVIEW Approved
01/19/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review