Review Details: COMMERCIAL TI

Permit Number - T07CM00208
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE CORRECT LOCATION ON TITLE PAGE.

2) PROVIDE SITE PLAN CLARIFYING ACCESSIBLE ROUTE INTO SPACE.
3) PROVIDE WATER FOUNTAIN.
4) BASED ON DIMENSIONS SQ. FOOTAGE OF SUITE SHOULD BE DIFFERENT.
02/28/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Air supplied to the nail area may not be recirculated. Reference Section 403.3 and Table 403.3, IMC 2003. Explain how this design prevents recirculation of the air from the nail areas.
02/28/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. If the appliances are provided with integral backflow devices, provide the 3rd party listing information that describes the backflow devices. The provided City of Los Angeles information does not appear to be related to the proposed foot spa units.
2. Show that the replaced RPBP has maintenance access. If backflow assemblies are located greater than five feet high, provide a work platform for the assemblies. Reference Section 603.3.4, UPC 2003.
3. Show the installation of the drinking fountain.
03/09/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
03/09/2007 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/09/2007 DELMA ROBEY APPROVAL SHELF Completed
03/09/2007 DELMA ROBEY OUT TO CUSTOMER Completed
03/09/2007 DELMA ROBEY REJECT SHELF Completed