Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM00208
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/28/2007 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE CORRECT LOCATION ON TITLE PAGE. 2) PROVIDE SITE PLAN CLARIFYING ACCESSIBLE ROUTE INTO SPACE. 3) PROVIDE WATER FOUNTAIN. 4) BASED ON DIMENSIONS SQ. FOOTAGE OF SUITE SHOULD BE DIFFERENT. |
02/28/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Air supplied to the nail area may not be recirculated. Reference Section 403.3 and Table 403.3, IMC 2003. Explain how this design prevents recirculation of the air from the nail areas. |
02/28/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. If the appliances are provided with integral backflow devices, provide the 3rd party listing information that describes the backflow devices. The provided City of Los Angeles information does not appear to be related to the proposed foot spa units. 2. Show that the replaced RPBP has maintenance access. If backflow assemblies are located greater than five feet high, provide a work platform for the assemblies. Reference Section 603.3.4, UPC 2003. 3. Show the installation of the drinking fountain. |
03/09/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
03/09/2007 | DROBEY1 | WWM | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/09/2007 | DELMA ROBEY | APPROVAL SHELF | Completed |
03/09/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
03/09/2007 | DELMA ROBEY | REJECT SHELF | Completed |