Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM00208
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/17/2007 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 01/17/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 01/18/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM00208 1/18/07 1. Water Heater takes 240V per Plumbing Fixture Schedule. Electrical plans show its power at 208V. Coordinate with Plumbing and clarify. 2. Conductor size used in fault calculation, #3, does not appear to apply to this installation. Please note that since the existing equipment appears to be series rated 65/10, a fault calculation may not be necessary. |
| 01/18/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide balancing data for the air conditionin system. 2. Air supplied to the nail area may not be recirculated. Reference Section 403.3 and TAble 403.3, IMC 2003. 3. Provide ventilation for the wax room. |
| 01/18/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE CODE ANALYSIS FOR ENTIRE BUILDING AND CLARIFY SEPERATED/NONSEPERATED USE. 2) RESTROOMS ARE NOT ACCESSIBLE PER 2003 ANSI A117.1. 3) PROVIDE SITE PLAN CLARIFYING ACCESSIBLE ROUTE INTO SPACE. 4) PROVIDE WATER FOUNTAIN. 5) CLARIFY SINK HEIGHTS KEYNOTE 6 FOR ANSI A117.1 COMPLIANCE. 6) PROVIDE 20% COST OF CONSTRUCTION BREAKDOWN ON PLANS PER SECTION 3409.6 OF 2003 IBC. 7) CORRECT APPLICABLE CODES TO REFLECT ANSI A117.1 INSTEAD OF ADAAG. 6) OCCUPANCY TYPE SPECIFIED IN PROJECT DATA IS INCORRECT, PLEASE CHANGE TO B. |
| 01/18/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/18/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Review the "Plumbing Requirements for Foot Spas" document an revise the installation drawings as required. 2. If the appliances are provided with integral backflow devices, provide the 3rd party listing information that describes the backflow devices. 3. Revise the plumbing drawing to coordinate with the architectural plans and the plumbing floor plan. 4. The applicable code is the 2003 UPC with local amendments. 5. All fonts shall be a minimum of 1/8", all uppercase. 6. Show how the water supply piping was sized. |
| 01/18/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 01/26/2007 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 01/26/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/26/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |