Review Date Reviewer's Name Type of Review Description Status Comments
01/17/2007 STEVE SHIELDS ZONING REVIEW Approved
01/17/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved
01/18/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM00208 1/18/07

1. Water Heater takes 240V per Plumbing Fixture Schedule. Electrical plans show its power at 208V. Coordinate with Plumbing and clarify.
2. Conductor size used in fault calculation, #3, does not appear to apply to this installation. Please note that since the existing equipment appears to be series rated 65/10, a fault calculation may not be necessary.
01/18/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide balancing data for the air conditionin system.
2. Air supplied to the nail area may not be recirculated. Reference Section 403.3 and TAble 403.3, IMC 2003.
3. Provide ventilation for the wax room.
01/18/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE CODE ANALYSIS FOR ENTIRE BUILDING AND CLARIFY SEPERATED/NONSEPERATED USE.
2) RESTROOMS ARE NOT ACCESSIBLE PER 2003 ANSI A117.1.
3) PROVIDE SITE PLAN CLARIFYING ACCESSIBLE ROUTE INTO SPACE.
4) PROVIDE WATER FOUNTAIN.
5) CLARIFY SINK HEIGHTS KEYNOTE 6 FOR ANSI A117.1 COMPLIANCE.
6) PROVIDE 20% COST OF CONSTRUCTION BREAKDOWN ON PLANS PER SECTION 3409.6 OF 2003 IBC.
7) CORRECT APPLICABLE CODES TO REFLECT ANSI A117.1 INSTEAD OF ADAAG.
6) OCCUPANCY TYPE SPECIFIED IN PROJECT DATA IS INCORRECT, PLEASE CHANGE TO B.
01/18/2007 ROBERT SHERRY WATER REVIEW Approved
01/18/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Review the "Plumbing Requirements for Foot Spas" document an revise the installation drawings as required.
2. If the appliances are provided with integral backflow devices, provide the 3rd party listing information that describes the backflow devices.
3. Revise the plumbing drawing to coordinate with the architectural plans and the plumbing floor plan.
4. The applicable code is the 2003 UPC with local amendments.
5. All fonts shall be a minimum of 1/8", all uppercase.
6. Show how the water supply piping was sized.
01/18/2007 MARTIN BROWN FIRE REVIEW Approved
01/26/2007 DROBEY1 WWM REVIEW Needs Review
01/26/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/26/2007 DELMA ROBEY OUT TO CUSTOMER Completed