Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM00195
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/16/2007 | MARTIN BROWN | FIRE | REVIEW | Denied | Correct all occupant loads on sheet X1.1 to 99. Some still show 107 to 108. |
04/19/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide structural details to show how the existing roof framing is to be modified for the new roof opening for the installation of the grease exhaust duct. Reference Section 302.1, IMC 2003. 2. Second request. Provide calculations demonstrating adequate ventilation for the new occupancy. Reference Section 401.2, IMC 2003. The use of ASHRAE 62.1-2004 is allowed per the local amendments to the 2003 IMC but it must be correctly used and the use of the default values for the occupant density (Table 6-1) are required. 3. Second request. Provide a mechanical design for the kitchen exhaust system (Type I hood, grease duct, and exhaust fan) including the equipment data, and the electrical operating information. Reference Section 301.6, IMC 2003. The design shall be included on a drawing sealed by an Arizona registrant. 4. Second request. Show that the clearances for the grease duct comply with Section 506.3.6, IMC 2003. Detail 1/M2 provides no dimensions, and it is lacking in construction details for the shaft. If the use of a fire-rated duct wrap is to be used instead of the shaft, show it being used in accordance with its listing. 5. Second request. Show that the clearances for the Type I hood comply with Section 507.9, IMC 2003. The code requires 18" of clearance between the hood and combustibles. (See the exception to Section 507.9 that allows for zero-clearances; any wood studs in the janitor's closet would prevent the use of the zero-clearance exception at that location.) 6. Second request. Show that the installation of the exhaust equipment for the Type I hood complies with Section 506.5, IMC 2003. (i.e. is the exhaust termination at least 10 feet from the property line) 7. The balancing data, shown on sheet M1, indicates that the make-up air unit is supplying only 80% of the specified exhaust air for the Type I hood. Show the source of the remaining make up air and indicate how it is to comply with Section 508.1, IMC 2003. 8. Second request. Show that the duct sealing method specified in mechanical note #9, sheet M2 complies with Section 803.2.8.1.2, IECC 2003. |
04/19/2007 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
04/20/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Clarify the relationship of the provided water supply isometric with the plumbing plan. Reference Section 103.2.3, UPC 2003. |
04/23/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Provide electrical requirements for the Exhaust Fan on the Mechanical Plans. SECOND REQUEST. SEE MECHANICAL COMMENT #3. 2. Provide electrical circuit for Item 8 on the Equipment Schedule on Sheet A1. SECOND REQUEST. This is a Reach-In Freezer located in the Basement, 115/60/1, 13.2A. 3. Provide electrical circuit for Item 8 on the Equipment Schedule on Sheet A1. SECOND REQUEST. This is a Self-Contained Walk-In Cooler, 1 HP Cond, 208-230/60/1, MCA 17, MOP 20, RLA 11.0. |
04/27/2007 | GERRY KOZIOL | WWM | REVIEW | Denied | NEEDS 8TH FLOOR CREDIT EVALUATION |
04/30/2007 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1: It appears exhaust duct work exceeds dimensioned width between trusses. New roof framing shall be required. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/03/2007 | BETH GRANT | OUT TO CUSTOMER | Completed |
05/03/2007 | SUE REEVES | REJECT SHELF | Completed |