Permit Number: T07CM00192
Parcel: 13110034A

Address:
5500 E 22ND ST

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T07CM00192
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/21/2007 ROBERT SHERRY WATER REVIEW Approved
03/21/2007 DAVE MANN FIRE REVIEW Approved
03/22/2007 GERRY KOZIOL WWM REVIEW Denied 1: WAL-MART
2: NEEDS TO PERMIT ON-SITE PRIVATE SEWER WASTEWATER PERMIT #PT07S00888
3: NEEDS MANHOLE CONSTRUCTION PERMIT (8TH FLR REVIEW/5TH FLR PERMIT) - NEED COPY OF PRIVATE SEWER FOR BASE MAP UPDATE (REF DEQ #P002707)
4: NEEDS WW/IWC REVIEW OF PHOTO OPERATION- TOM TOMCHAK 579-5771 - 5025 W INA ROAD
04/02/2007 TERRY STEVENS ZONING REVIEW Denied 04/02/07

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site/development plan. Additional comments may be forthcoming.
04/02/2007 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed There is 3000 sf added to this old site because they enclosed a breezeway.
Impact fees $6,014
04/09/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied The building plan will not be approved untill all applicable reviewing sections have approved the site plan; zoning, landscape, plumbing, fire and engineering. Once this process has been complete, submit 2 copies of the CDRC approved development plan that also have site plan approval with the building plan set.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/20/2007 DELMA ROBEY OUT TO CUSTOMER Completed
04/20/2007 SUE REEVES REJECT SHELF Completed