Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM00172 1/26/07

1. Fixture F1 is damp location listed according to the cut sheet. In its intended location it should be wet listed.
2. Please demonstrate that the fixture intended for K1 is wet-listed.
3. From the drawings and cut sheet, it appears that Fixture K1 has two lamps. Outdoor Lighting Code Compliance only accounts for one.
01/26/2007 DROBEY1 MECHANICAL-COMMERCIAL REVIEW Needs Review