Permit Number: T07CM00172
Parcel: 127070080

Review Status: Completed

Review Details: OTHER

Permit Number - T07CM00172
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide a floor plan to indicate the rooms shown on the ventilation calculations and which mechanical unit is supplying which area. Reference Section 106.3.1, IMC 2003.
2. Show that adequate make-up air is being provided for the dryer. Reference Section 504.5, IMC 2003.
3. Show that no recirculation of air will occur from the restrooms. Reference Section 403.2.1, IMC 2003.
4. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
5. Provide a plumbing design for the water being provided to the humidifier. Reference Section 106.3.1, IMC 2003.
01/24/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review