Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T07CM00172
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/24/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide a floor plan to indicate the rooms shown on the ventilation calculations and which mechanical unit is supplying which area. Reference Section 106.3.1, IMC 2003. 2. Show that adequate make-up air is being provided for the dryer. Reference Section 504.5, IMC 2003. 3. Show that no recirculation of air will occur from the restrooms. Reference Section 403.2.1, IMC 2003. 4. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 5. Provide a plumbing design for the water being provided to the humidifier. Reference Section 106.3.1, IMC 2003. |
| 01/24/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |