Permit Number: T07CM00158
Parcel: Unknown

Address:
2540 E 10TH ST

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T07CM00158
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/22/2007 MARTIN BROWN FIRE REVIEW Approved
01/24/2007 PETER MCLAUGHLIN PLANNING-CITY HALL REVIEW Denied Revise all site plans and elevation drawings to demonstrate compliance with SE-06-41 Special Exception condition #2, which reads: "The replacement pole shall not exceed 40 feet in height." The submitted plans and elevations show a dimensioned height of 40 feet, 3-5/8 inches.
01/29/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
02/09/2007 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: T-Mobile - 2540 E. Broadway Blvd.
T07CM00158
Site Plan (1st Review)

TRANSMITTAL DATE: February 6, 2007

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Provide a copy of the last approved site plan for this property. Addition comments may be forth coming.

2. The Special Exception review must be completed and approved prior to zoning approval of the building plan.

3. Show all easements of record on the plan. If not already in place an easement will be required from the proposed T.E.P pole to the proposed enclosure.

4. The area shown as the proposed T-Mobil parking space needs to be paved. It is unclear on the plan, please clarify.

5. Per Ordinance No. 10362 Condition #2 the replace pole shall not exceed 40 feet in height. The plan shows 40'-3 5/8" high.

6. Per Ordinance No. 10362 Condition #3 add a note to the plan stating that "THE REPLACEMENT POLE SHALL BE PAINTED TO MATCH EXISTING POLES IN THE AREA".

7. Per Ordinance No. 10362 Condition #4 add a note to the plan stating that "THE MASONRY WALL SURROUNDING THE LEASE SITE SHALL BE TEXTURED AND PAINTED TO MATCH OTHER BUILDINGS IN THE IMMEDIATE VICINTY".

8. Per Ordinance No. 10362 Condition #5 add a note to the plan stating that "ALL WALLS VISIBLE FROM A PUBLIC RIGHT-OF-WAY AND/OR ADJACENT OT EXISTING RESIDENTIAL DEVELOPMENT, ARE TO BE GRAFFITI-RESISTANT AND INCORPORATE ONE (1) OR MORE VISUALLY APPEALING DESIGN TREATMENTS, SUCH AS THE USE OF TWO (2) OR MORE DECORATIVE MATERIALS LIKE STUCCO, TILE, STONE, OR BRICK; A VISUALLY INTERESTRING DESIGN ON THE WALL SURFACE; VARIED WALL ALIGNMENTS, (JOG, CURVE, NOTCH, SETBACK, ETC); AND/OR TREES AND SHRUBS IN VOIDS CREATED BY THE WALL VARIATIONS".

9. Per Ordinance No. 10362 Condition #6 add a note to the plan stating that "SIX (6) INCH FENCE BLOCK OR GREATER SHALL BE USED FOR PERIMETER WALLS".

10. Per Ordinance No. 10362 Condition #3 add a note to the plan stating that "ANY RELOCATION, MODIFICATION, ETC., OF EXISTING UTILITIES AND/OR PUBLIC IMPROVEMENTS NECESSITATED BY THE PROPOSED DEVELOPOMENT WILL BE AT NO EXPENSE TO THE PUBLIC".

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 791-5608 ext. 1180.

C:\planning\site\t07cm00158.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised plan and additional requested documents
02/14/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
02/16/2007 JAY HOGAN COMMUNICATIONS REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/14/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
06/14/2007 SUE REEVES REJECT SHELF Completed