Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM00123
Parcel: 13819029C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM00123
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2007 MARTIN BROWN FIRE REVIEW Approved
01/10/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise all fonts to be a minimum of 1/8", all upper case.
2. Show that the space has adequate ventilation per Secton 401, IMC 2003.
3. Show that the operation of the exhaust fan for the restroom will not result in recirculation of air from the restroom to the ofice space.
4. Provide insulation for the ductwork per Section 803.2.8, IECC 2003.
01/10/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM001232 1/10/07

1. Since Fault #1 is greater than 10,000 AIC, it appears that Phael CHL is not properly rated. Please clarify.
2. Please note that the minimum font size is 1/8". Since this is a small job we will pass it if this poses an undue inconvenience on the engineering firm at this time, but keep it in mind for future projects.
01/10/2007 ROBERT SHERRY WATER REVIEW Approved
01/10/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise all fonts to a minimum of 1/8", all upper case.
2. Revise the water fiture units per Table 6-4, UPC 2003.
01/16/2007 DROBEY1 WWM REVIEW Needs Review
01/16/2007 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review
01/16/2007 DROBEY1 ENGINEERING REVIEW Needs Review
01/16/2007 DROBEY1 ZONING REVIEW Needs Review
01/16/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/16/2007 DELMA ROBEY OUT TO CUSTOMER Completed