Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM00113
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/03/2007 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 07/03/2007 | CLAYTON TREVILLYAN | BUILDING-RESIDENTIAL | REVIEW | Approved | |
| 07/05/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Photovoltaic Line Diagram refers to Note 1. There is no Note 1. Perhaps there is a missing sheet. 2. Specify which panel is to be installed, Model and Catalogue Number, on the Photovoltaic Line Diagram. 3. Demonstrate compliance with NEC 690.14 (C) (2). 4. Specify the warning sign required by NEC 690.17 Provide the exact wording. 5. Specify the marking required by NEC 690.53. Provide the exact wording. |