Permit Number: T07CM00100
Parcel: 133300210

Address:
8831 E SHILOH PL

Review Status: Completed

Review Details: OTHER

Permit Number - T07CM00100
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/21/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: May 21, 2007
ACTIVITY NUMBER: T07OT00785 / T07CM00100
PROJECT NAME: Ilzar Residence Garage/Workshop
PROJECT ADDRESS: 8831 East Shiloh Place
PROJECT REVIEWER: Patricia Gilbert

FLOODPLAIN USE PERMIT IS DENIED

RESUBMITTAL REQUIRED: SITE PLAN, , FLOODPLAIN USE PERMIT APPLICATION

HYDROLOGY REPORT IS APPROVED

1. The submitted Hydrology Report shows the erosion hazard setback (EHS) at 8.4' from the property line. The site plan shows the addition 6.8' from the property line. Structures can not be placed with the EHS. The addition must placed outside the EHS. This office recommends to place the addition 9' from the property line. Revise the site plan to show the addition outside the EHS.

2. Provide a general note to the site plan stating this property is subject the Floodplain Ordinance Chapter 26.