| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/21/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM00999 5/21/08 1. Approved Plumbing plans call for a 4500W, 240V Water Heater. Submit revision to these plans consistent with Electrical 3400W, 208V power requirements. 2. Approved Mechanical plans call for a 12A, 230V Evaporative Cooler. Submit revision to these plans consistent with 208V power requirements. 3. Approved Mechanical plans specify a 230V Heat Pump Split System. Submit revision to these plans consistent with Electrical 208V power requirements. |