Permit Number: T07CM00099
Parcel: 124161490

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T07CM00099
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/23/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Second request. See keynotes 20 and 37 on sheet A101. Building sewers that do not fall under the conditions for General Permit 4.01 (e.g. serve a single building, no lift station, no manhole) shall be designed and built per the 2003 Uniform Plumbing Code.
05/24/2007 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Metal Building for 1001 S. Tyndall Ave.
T07CM00099
Site Plan (1st Review)

TRANSMITTAL DATE: May 24, 2007

COMMENTS: Please resubmit revised drawings along with a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for full code compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC).

2. This comment was not fully addressed. Copies of the approved and recorded Pima County Tax Parcel Combo and a Covenant Regarding Development and Use of Real Property must be provided prior to Zoning approval of the site plan. This project is comprised of two (2) separate parcels with the proposed building to be constructed across the property lines. Prior to approval of the site plan the parcels will need to be combined. Provide a Pima County Tax Parcel Combo and a Covenant Regarding Development and Use of Real Property which has been recorded at the Pima County Recorders Office.

3. This comment was not fully addressed. The mounting height of the sign is 7'-0" to bottom of sign.D.S. 2-02.2.1.A.8 Per E8 TYPICAL PARKING LAYOUT PLAN there is a note for the "DISABLED PARKING SIGN FOR STANDARD VEHICLE OR VAN ACCESSIBLE SPACE AS NOTED ON PLAN", there is no note on the site plan showing the location of the sign. The pole mounted sign as shown on the detail will not work for this application. Provide a detail for the sign, see attached.

4. Zonings comment about the DSMR was in error. It should have read "A DSMR may be required, see engineering comments. Provide a copy of the approval letter from solid waste. D.S. 2-02.2.1.A.32 Zoning acknowledges that 90 gal. roll off refuse containers are proposed for this project. A DSMR will be required for the use of the roll off refuse containers. Also written approval from Solid Waste is required.

5. Ensure that all changes to the site plan are reflected on the landscape & grading plan.

6. Zoning will provide an over the counter review once the above comments have been addressed. Please call or email to set and appointment.


If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\site\t07cm00099-2nd.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
05/24/2007 STEVE SHIELDS ZONING HC SITE REVIEW Approved
06/07/2007 ANDREW CONNOR NPPO REVIEW Approved Exception
06/07/2007 ANDREW CONNOR LANDSCAPE REVIEW Approved
07/25/2007 LOREN MAKUS ENGINEERING REVIEW Denied DATE: July 25, 2007
FROM: Loren Makus, EIT
Engineering Division

SUBJECT: 1001 S. Tyndall Ave.
Metal Warehouse
Site Plan T07CM00099 (Second Review)

RESUBMITTAL REQUIRED: Site Plan.

The Site Plan cannot be approved as submitted. Please include a response letter to the comments below along with the corrected copies of the Site Plan with your next submittal.

Site Plan:
1. Provide the Basis of Bearings (DS 2-02.2.1.A.5). (Clearly identify the location of the change in your response letter.)
2. Complied.
3. Provide the sight visibility triangle (SVT) with a 20-foot stem along 20th St. and the185-foot nearside leg on Tyndall Ave. (DS 2-02.2.1.A.10).
4. Accepted per e-mail from Matt Flick 4-17-07
5. Complied
6. Complied
7. Complied
8. Complied
9. Complied
10.Complied

Please do not hesitate to contact me with any questions.

Loren Makus, EIT
Senior Engineering Associate
(520) 837-4927
loren.makus@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
07/30/2007 DELMA ROBEY OUT TO CUSTOMER Completed