Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM00099
Parcel: 124161490

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM00099
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/23/2007 ROBERT SHERRY WATER REVIEW Approved
05/24/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The applicable code for all commercial plumbing projects is the 2003 Uniform Plumbing Code with Local Amendments.
2. Provide an upper terminal cleanout for the water closet. Reference Sections 707.4 and 707.11, UPC 2003.
3. Provide vent piping of sufficient size to comply with Section 904.1, UPC 2003.
4. An appeal to the building official must be approved prior to approval of the plans. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2003, for B and S1 occupancies.
5. The water heater thermostat may not be used to provide scald protection for a public lavatory. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003.
6. Second request. If the specified water heater is not supplied with integral heat traps, provide 0.5" of insulation with a maximum conductivity of 0.27 btu per inch/h °F on the first 8 feet of supply and discharge piping. Reference Section 804.5, IECC 2003.
05/24/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Recirculation of ventilation air from toilet rooms is prohibited. Reference Table 403.2.1 (3), IMC 2003.
05/24/2007 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Metal Building for 1001 S. Tyndall Ave.
T07CM00099
Building Plan (2nd Review)

TRANSMITTAL DATE: May 24, 2007

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t07cm00099.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
06/19/2007 WILDAN BUILDING-COMMERCIAL REVIEW Denied June 19, 2007

City of Tucson Development Services
P.O. Box 27210
Tucson, AZ 85726

RE: Tyndall Avenue Metal Building – 2nd REVIEW
CITY OF TUCSON LOG NO. T07CM00099
WILLDAN PROJECT NO. 13881-7007

The second review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all corrections and revisions must be made on the original plans and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2003 IBC, 1997 UAC, 2003 IMC, 2003 IECC, ANSI 117.1-2003, 2002 NEC with local modifications, and the 2003 UPC. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Chris Kiel.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
B/S1 14 VB 5000 No No

Special Inspection is required for the following items:
* - Special inspections may be required once structural documents have been provided.

The following items are acceptable for deferred submittals:
Metal building

GENERAL COMMENTS:
Reviewed and accepted.

ARCHITECTURAL COMMENTS:
Sheet A101
Please provide additional information regarding the rear exit in order to verify that an accessible means of egress to the public way has been provided per section 1007 of the 2003 IBC. Comment remains: Two (2) exits are required due to the travel distance is over 100’ per. Section: 1013.3 and 1014.1 IBC 2003.

Please provide a drinking fountain per table 2902.1 of the 2003 IBC. Accessible information regarding the drinking fountain is provided on sheet G101, but the plans do not provide one. Comment remains: Please provide the signed appeal form at time of the next review.

Sheet A201
Please provide wall protection around the water closet per section 1210.2 of the 2003 IBC. Comment remains. Not addressed.

Sheet E201
Please provide exit signage per section 1011 and egress illumination with emergency power per section 1006.3 of the 2003 IBC, as two exits are required per section 1014.1 (common path of egress travel exceeds 75’). Please be sure to include the emergency power for the exterior illumination at the exit discharge immediately adjacent to the exit. Comment remains. Not addressed.

ACCESSIBILITY COMMENTS:
Please refer to the Architectural Comments for issues concerning accessibility.



Sincerely,

WILLDAN




Chris Kiel, C.B.O., M.C.P.
Building Official

CEK/jk

Final Status

Task End Date Reviewer's Name Type of Review Description
07/30/2007 DELMA ROBEY OUT TO CUSTOMER Completed
07/30/2007 SUE REEVES REJECT SHELF Completed