Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM00099
Parcel: 124161490

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T07CM00099
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2007 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Metal Building for 1001 S. Tyndall Ave.
T07CM00099
Building Plan (1st Review)

TRANSMITTAL DATE: January 12, 2007

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 791-5608 ext. 1180.

C:\planning\grading\t07cm00099.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
01/26/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
01/26/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The 2003 International Mechanical Code with Local Amendments is the relevant code for this project.
2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
3. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference Section 803.2.8, IECC 2003.
4. Coordinate the envelope energy calculations with the building design to demonstrate compliance with the energy conservation code. The calculations call out continuous R-19 insulation for the roof and walls of the entire building but the drawings show no roof insulation and wall insulation only in the office area. Reference Section 104.2, IECC 2003.
5. Show how the equipment is being supported from the building structure and in accordance with the conditions of its listing and the manufacturer's installation requirements. Reference Sections 302.1 and 304.1, IMC 2003.
6. Revise detail 104/M201 to show how the flues for the unit heaters are to be installed on this building. Reference Section 510.6, UPC 2003.
7. Provide calculations demonstrating adequate ventilation. Reference Sections 403.1, 403.3.3, and 403.3.2, IMC 2003.
8. Show how outside air is to be supplied to FC-1. Reference Section 106.3.1, IMC 2003.
9. Provide power at the correct voltage to the evaporative coolers per the manufacturer's installation instructions. Reference Section 304.1, IMC 2003.
01/29/2007 ROBERT SHERRY WATER REVIEW Denied Provide the size of the water meter along with the size and location of the backflow assembly. Reference Section 103.2.3, UPC 2003.
01/29/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. Provide waste and vent isometrics. Reference Section 103.2.3, UPC 2003.
3. Provide fixture descriptions for all plumbing fixtures. Reference Section 401.1, UPC 2003.
4. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2003, for B and S1 occupancies.
5. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference Section 310.0, UPC 2003.
6. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003.
7. Provide access and working space for the water heater. Reference Sections 306.1 and 306.3, IFGC 2003.
8. The design of the water heater piping, with a shutoff valve located between the water heater and the expansion tank, makes it impossible for the expansion tank to accommodate the thermal expansion of the water in the water heater, as intended by Section 608.3, UPC 2003. Reference Section 505.6, UPC 2003.
9. Provide a drain to an approved location from the watertight pan under the water heater. Reference Section 508.4, UPC 2003.
10. If the specified water heater is not supplied with integral heat traps, provide 0.5" of insulation with a maximum conductivity of 0.27 btu per inch/h °F on the first 8 feet of supply and discharge piping. Reference Section 804.5, IECC 2003.
02/02/2007 GERRY KOZIOL WWM REVIEW Approved
02/05/2007 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed impact fees do apply, no site/development plan submitted within deadline
5000 sf
central district
$3975.08
02/22/2007 WILDAN BUILDING-COMMERCIAL REVIEW Denied February 21, 2007



City of Tucson Development Services
P.O. Box 27210
Tucson, AZ 85726

RE: Tyndall Avenue Metal Building
CITY OF TUCSON LOG NO. T07CM00099
WILLDAN PROJECT NO. 13881-7007 – 1ST REVIEW

The initial review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all corrections and revisions must be made on the original plans and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2003 IBC, 1997 UAC, 2003 IMC, 2003 IECC, ANSI 117.1-2003, 2002 NEC with local modifications, and the 2003 UPC. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Chris Kiel.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
B/S1 14 VB 5000 No No

Special Inspection is required for the following items:
* - Special inspections may be required once structural documents have been provided.

The following items are acceptable for deferred submittals:
Metal building

GENERAL COMMENTS:
General
A deferred submittal letter for the metal building will need to be forwarded directly to the Building Official and approved. Reference the City of Tucson Submittal Policy.

Please revise the denoted codes to those currently adopted by the City of Tucson (i.e. 2003 IMC, 2003 IECC, ANSI 117.1-2003, 2003 UPC, etc.).

ARCHITECTURAL COMMENTS:
Sheet A101
Please provide additional information regarding the rear exit in order to verify that an accessible means of egress to the public way has been provided per section 1007 of the 2003 IBC.

Please provide additional information regarding the lavatory in order to verify compliance with section 606 of ANSI 117.1-2003.

Please provide a drinking fountain per table 2902.1 of the 2003 IBC. Accessible information regarding the drinking fountain is provided on sheet G101, but the plans do not provide one.

Remove the designation for door 106C indicating that it is optional per section 106.1.1 of the 2003 IBC and the City of Tucson policy (options are not permitted for commercial projects).

Sheet A201
Please provide wall protection around the water closet per section 1210.2 of the 2003 IBC.

Sheet E201
Please provide exit signage per section 1011 and egress illumination with emergency power per section 1006.3 of the 2003 IBC, as two exits are required per section 1014.1 (common path of egress travel exceeds 75’). Please be sure to include the emergency power for the exterior illumination at the exit discharge immediately adjacent to the exit.

Sheet G101
Please revise the height for the vertical grab bar to comply with section 604.5.1 of ANSI 117.1-2003 (i.e. 39-41”).

COMcheck
Please revise the building envelope COMcheck to verify compliance with the 2003 IECC as adopted by the City of Tucson. In addition, please provide a COMcheck for the mechanical and electrical lighting systems per section 104.2 of the 2003 IECC. Finally, please coordinate the information between the plans and the submitted COMcheck per section 106.1.1 of the 2003 IBC (i.e. only the offices appear to be insulated). Specify the R and U-values on the plans.

STRUCTURAL COMMENTS:
General
Please provide structural plans and calculations for the installation of the prefabricated metal building and associated foundation system. The current submittal fails to provide any information regarding the structural system. Reference IBC Section 106.1.1.

PLUMBING COMMENTS:
Reviewed by others.

MECHANICAL COMMENTS:
Reviewed by others.

ELECTRICAL COMMENTS:
Reviewed by others.

ENERGY CODE COMMENTS:
Reviewed by others.

ACCESSIBILITY COMMENTS:
Please refer to the Architectural Comments for issues concerning accessibility.

Sincerely,

WILLDAN




Martin Haeberle, C.B.O.
Building Official

MAH/tb

Final Status

Task End Date Reviewer's Name Type of Review Description
05/21/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
05/21/2007 SUE REEVES REJECT SHELF Completed