Permit Number: T07CM00094
Parcel: 134180100

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM00094
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2007 STEVE SHIELDS ZONING REVIEW Approved
01/08/2007 ANY ENGINEERING REVIEW Approved
01/08/2007 DAVE MANN FIRE REVIEW Approved
01/09/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
01/18/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide a mechanical plan, including ventilation calculations for the new occupancy.
01/18/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) SEPERATE MENS AND WOMENS RESTROOM FACILITIES REQUIRED PER CHAPTER 29 OF 2003 IBC. ACCESSIBLE ROUTE SHOULD NOT GO THROUGH BREAKROOM (SEC. 1104.3 OF 2003 IBC)
2) PROVIDE FRAMING DETAILS.
3) SHOW ACCESSIBLE ROUTE INTO BUILDING .
4) PROVIDE VALUATION.
5) SHOW ON DRAWINGS HOW 20% COST OF CONSTRUCTRION PER SECTION 3409.6 OF 2003 IBC HAS BEEN MET.
6) CLARIFY BREAKROOM COUNTER HEIGHT PER 2003 ANSI A117.1.
01/18/2007 ROBERT SHERRY WATER REVIEW Approved
01/18/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show revised plumbing plan to coordinate with the architectural comments.
2. A 2" trap and trap arm cannot be used with a lavatory with a 1-1/4" tailpiece. The largest trap and trap arm that may be used is 1-1/2".
01/18/2007 DROBEY1 WWM REVIEW Needs Review
01/18/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/18/2007 DELMA ROBEY OUT TO CUSTOMER Completed