| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/05/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM00089 1/5/07 1. The pole submittal does not reference any current Detail in the City of Tucson Standard Details for Public Improvements. 2. Information on the foundation is not sufficient. Unless a current Standard Detail is referenced for both the pole and foundation, a detail and calculations for both the pole and foundation shall be generated and sealed by a Registered Structural Engineer. 3. Provide electrical circuits for the new cameras and the new luminaires. Reference panel and circuit number. 4. Indicate the location of the electrical panel. 5. Indicate the voltage, ampere rating, and phase of the electrical panel. 5. Provide a Lighting Fixture Schedule. 6. Demonstrate compliance with the Tucson Lighting Code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf. 7. Provide two sets of plans. |
| 01/08/2007 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 01/08/2007 | ANY | ENGINEERING | REVIEW | Approved |