Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T07CM00073
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/08/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 01/09/2007 | JAY HOGAN | COMMUNICATIONS | REVIEW | Approved | |
| 01/09/2007 | PETER MCLAUGHLIN | PLANNING-CITY HALL | REVIEW | Denied | Revise plans, elevation drawings and details and submit all necessary documents to demonstrate compliance with Special Exception conditions a. through f. as follows: a. The face of the each array shall be no greater than 9 feet in length. Standoff arms shall be no longer than necessary to this length. Provide fully dimensioned drawings to demonstrate compliance with this requirement. b. Dimension pole diameter at base, top, and point of attachment. c. Wire ports shall be no higher or lower than the antenna panels. Cables shall be routed through the interior of the pole, and shall not be visible. d. Prior to issuance of any permits, the applicant shall demonstrate that the existing monopole and related cellular communications equipment are in compliance with all zoning and building code requirements. e. All new pole-mounted equipment shall be painted to match the existing pole. f. A maximum of four (4) new antennae are to be provided as part of this Special Exception application. |
| 01/12/2007 | TERRY STEVENS | ZONING | REVIEW | Denied | 01/12/07 Development Services Department Zoning Review Section Terry Stevens Lead Planner Comments: 1. The Cell Tower site plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Special Exception section of DSD. 2. Provide a copy of the last stamped and approved site plan for the existing cell tower. 3. Based on the last approved site plan further comments may be forth coming. |
| 01/19/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE STRUCTURAL CALCULATIONS FOR FBB SHELTER FOUNDATION DESIGN. 2) PROVIDE STRUCTURAL CALCULATIONS FOR ICE BRIDGE POST AND COAXIAL CABLE BRIDGE. 3) PROVIDE STRUCTURAL CALCULATIONS FOR MONOPOLE WITH ALL ANTENNA SECTOR BRACKETS AND ANTENNA ATTACHED. 4) PROVIDE STRUCTURAL CALCULATIONS AND MOUNTING DETAILS FOR ANTENNA SECTOR BRACKETS, NEW ANTENNAS, AND ANTENNA MOUNTING BRACKETS. |
| 01/25/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Provide an electrical circuit for the lighting fixture indicated on Sheet A-5, Detail 4. 2. The incandescent lighting fixture indicated on Sheet A-5, Detail 4 does not comply with the 2003 IECC, Section 805.6. 3. Demonstrate compliance with the Tucson Lighting Code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf. 4. It appears that the generator plug is drawn on the wrong side of the building on the Grounding Plan and Electrical Site Plan. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/22/2007 | FSANCHE1 | OUT TO CUSTOMER | Completed |
| 02/22/2007 | SUE REEVES | REJECT SHELF | Completed |