07/23/2007 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS for Activity # T07CM00072

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

As of 9-02-04 the City of Tucson has adopted the 2003 IRC with the exception of the plumbing portion which has been replaced with the 2003 UPC with amendments. All plans should reference these codes. See this site for all adopted amendments: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html

Construction drawing guidelines are available from the residential desk of the Development Services Division.

All information must be legible with a minimum 1/8" lettering:

All dimensions and notes shall be consistent on each plan or elevation with appropriate detail references.

Provide consecutively numbered sheet numbers on each construction drawing (all information is to appear on the drawings), R106.1.1.

SITE PLAN:

1. Show the water pipe size on the drawings from the meter to the building. Show the point of connection for the proposed branch. The pipe must be sized for the calculated load, 2003 UPC 610.1.

FLOOR PLANS:

1. Exterior walls (Unit #2 North wall) with a fire separation distance less than 3-foot shall have not less than one-hour fire-resistive construction. Show compliance with R302.1 by providing a section detail of materials prescribed in IBC Table 720.1(2), Items 15-1.1 to 15-1.16.
2. Projections (overhangs) may not extend to a point closer than 2 feet from the property line, and when extending into the 3-foot fire separation distance shall have not less than one-hour fire-resistive construction on the underside. Provide a detail or notation showing compliance with R302.1. Show an elevation profile of the North wall overhang with one hour rated protection.
3. Opening (windows & doors) are not permitted of an exterior wall with a fire separation distance less than 3-foot, R302.2. Provide a detail or notation showing compliance with R302.2 by relocating or blocking Unit #2 Kitchen door and Bathroom window (may replace with exhaust fan).
4. Provide all window sizes and types, and designate the operable portion of windows, as well as the location of tempered glass (within 24" of doorways), R303.1, R308.4 & R310. Detail materials used for blocking all openings.
5. Individual dwelling units in duplexes must be separated by a 1-hour firewall from floor to bottom of roof sheathing. Provide a detail or notation showing materials proving compliance, R317.1.

STRUCTURAL PLANS:

1. Provide complete framing plans showing material sizing and spacing on the drawing. Show the size of all new opening. Show size and span of all new opening headers consistent with Table 502.5(1). Identify load bearing wall conditions.
2. Show the size, spacing and connections of new wall framing members. Show the furred-out wall connections and insulation amount on the drawings.

SECTIONS - DETAILS - MISC. NOTES:

1. Show any wood framing members resting on concrete as pressure treated (wall sill plates), R319.1(2).

PLUMBING PLANS:

1. The City of Tucson has adopted the 2003 Uniform Plumbing Code with state amendments (ARIZONA STATE PLUMBING CODE). The plans should reference this code. Show all plumbing on a construction drawing.
2. Provide a plan view showing the water supply line diameter and point of connection for the new lines. Maintain the yard pipe size to the water heater or first bathroom group.

ELECTRICAL PLANS:

1. Show all electrical information on a construction drawing.


If you have any questions, please contact your assigned plans examiner Ken Van Karsen at 791-5550, extension 1112.