Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T07CM00069
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/20/2007 | GERRY KOZIOL | WWM | REVIEW | Denied | NEEDS 8TH FLOOR WW CREDIT EVALUATION FOR DEMO OF EXSISTING STRUCTURE & REMOVAL OF TEMP MODULAR |
| 02/20/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/23/2007 | ROBERT SHERRY | WATER | REVIEW | Denied | Revise the site drawing to show the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Note that Tucson Water does not provide ¾" water meters and that the water supply to the building is shown as 1" on sheet P1.0 and 1-1/4" on sheet P2.0. Reference Section 103.2.3, UPC 2003. |
| 03/02/2007 | SUZANNE BOHNET | ENGINEERING | REVIEW | Denied | Prior to building plan approval, a site application card (yellow card) with the CDRC approved development plan must be stamped with signatures for DSD site approval by the following reviewing sections; Fire, Zoning, Handi-cap, Engineering, and Landscape/NPPO. Provide two copies of the site approved development plan, landscape and NPPO plans with the approved building plan set. The development plan may be walked through for stamps and site card sign off. No fees are involved in re-stamping the development/tentative plat plans as an approved site plan. |
| 03/08/2007 | STEVE SHIELDS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Washington Federal Savings T07CM00069 Building Plan (1st Review) TRANSMITTAL DATE: March 8, 2007 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed. 2. Zoning could not verify that the building plan was in compliance with the approved Development plan. 3. A site card with DSD approvals by Fire, Zoning, Handi-cap, Engineering, and Landscape/NPPO including the approved development plan stamped for site plan approval and signatures is required before the building plan can be approved by Zoning. Two copies of the approved site/development plan, landscape and NPPO plans are to be submitted with the building plans packet for processing and approval as a site plan. No fees are involved in re-stamping the development/tentative plat plans as an approved site plan. The development plan may be walked through for stamps and site card sign off. Submit the following: two copies of the stamped development plan, landscape and NPPO plans must be included with the site plans packet processed together for site approval. 4. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 791-5608 ext. 1180. C:\planning\grading\t07cm00069.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents |
| 03/19/2007 | BETSY COTTLE | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/20/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 06/20/2007 | SUE REEVES | REJECT SHELF | Completed |