Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM00016
Parcel: 135084520

Address:
7150 E 22ND ST

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T07CM00016
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/18/2007 ROBERT SHERRY WATER REVIEW Denied 1. Tucson Water will no longer allow water meters and backflow preventers to be manifolded to achieve additional capacity.
2. Revise the site utility plan to show the location of the reduced pressure backflow assembly on the drawings, specify the reduced pressure backflow assembly being installed, and indicate the size of the assembly. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
06/19/2007 MARTIN BROWN FIRE REVIEW Denied Please add the following automatic sprinkler criteria to the plans:

1. The hazard classification of the occupancy including any special hazards.
2. The design standard to be used.
3. The availability and adequacy of the water supply.
4. The design density and the area of operation.

Also, note on Civil, Sheet 3, seems to indicate a 2" fire service line. Please review and verify will be large enough.
06/21/2007 TERRY STEVENS ZONING REVIEW Denied 06/21/07

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming.
06/21/2007 SREEVES1 WWM REVIEW Denied 1:DESERT TOYOTA
2:NEEDS WASTEWATER IWC REVIEW-TOM TOMCHAK 579-5771 5025 W INA RD.(SAND/OIL INTERCEPTORS, RAINWATER INTURSION, ETC) CANNOT DISCHARE 2" ELEVATOR SUMP DRAIN TO FS SHOWN ON DRAWING P2.1C
3:NEED TO PERMIT ON-SITE PRIVATE SEWER-NEED DEQ APPROVAL TO CONSTRUCT IF OVER 3000 GAL/DAY-NEED WASTEWATER 8TH FLOOR APPROVAL FOR MANHOLE TAP (G-71-032) AND MANHOLE CONSTRUCTION (G-62-081) -NEED 5TH FLOOR MANHOLE CONSTRUCTION & MANHOLE TAP PERMIT- NEED COPY OF ON-SITE PRIVATE SEWER FOR BASE MAP UPDATE.
4:NEED 8TH FLOOR CREDIT EVALUATION FOR DEMO OF EXSISTING BLDGS PER DRAWINGS.
07/06/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed Impact Fee's Do Apply; East District; 61,523 Square Feet of Office Space; 27,641 Square Feet of Repair Facility; $173,547.33

* 126,980 Square Feet of Parking Garage not included in Impact Fee's
07/27/2007 MATT FLICK ENGINEERING REVIEW Approved The following comment has been satisfactorily addressed:

Floodplain permit review approval required prior to post-3rd party review.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/31/2007 THAUSER1 OUT TO CUSTOMER Completed
07/31/2007 SUE REEVES REJECT SHELF Completed