Permit Number: T07BU02627
Parcel: 126042730

Address:
1034 N JERRIE AV

Review Status: Completed

Review Details: GRADING

Permit Number - T07BU02627
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2008 JASON GREEN ENGINEERING REVIEW Denied DATE: January 4, 2008
SUBJECT: 1044 N Jerrie Avenue Grading Plan- 1st Engineering Review
TO: DOWL Engineering Attn: Rudolf A. Ing, P.E.
LOCATION: T14S R14E Sec10 Ward 6
REVIEWERS: Jason Green, CFM
ACTIVITY: T07BU02627 (Grading Plan)


SUMMARY: Engineering Division of Development Services Department has received and reviewed the grading plan (T07BU02610), Drainage Statement (DOWL Engineers, 18JUL06) and the last approved site plan for the above referenced property. Engineering Division does not recommend approval of the grading plan at this time. The following items need to be addressed:


GRADING PLAN COMMENTS:

1) DS Sec.11-01.9: Revise the grading plan and cross sections A-D to provide the required 2-feet setback from all property boundaries to the top of fill slope for the water harvesting area, the rock riprap erosion protection and/or the proposed wall. Provide and/or revise the cross-sections on the grading plan to show the limits of grading, property lines and the required 2-feet setback from the property lines to limits of grading.

2) DS Sec.3-05: Verify how the parking lot is constructed along the northeast side of the project just north of the refuse location. Label 6-inch curbs or provide wheel stops to prevent vehicles from driving off the vehicular use area and damaging the landscaping.

3) Revise the grading plan to correctly show the location for Keynote #34. The rock riprap drainage swale is shown along the north and south portion of the site, however the Keynote call out for #34 is shown in the middle of the large water-harvesting basin. Revise the call out to correctly show the location of the drainage swale for clarity.

4) Revise Details A, B, and C to provide the method of placement (hand placed, dumped, grouted) for the proposed rock riprap located within the drainage swales.

5) DS Sec.2-02.2.1.A.8: Revise the grading plan to correctly label the 2.5-foot overhang within the proposed parking spaces along the north portion of the vehicular use area. Per Sheet C1.0 the space is dimensioned at 2.43-feet not the required 2.5-feet.

6) DS Sec.2-02.2.1.A.12: Revise Detail #8 for the handicap ramp on Sheet C1.2 of the grading plan to show the proper handicap ramp required for the PAAL ingress/egress from Jerrie Avenue. Per COT Standard Detail 207 the alternative detail that is shown on the top half of Sheet 4 of 5 is the correct handicap ramp required for this location. Provide all dimension for the ramp and verify that the revision meets the design requirements per ANSI Standards A117.1-2003 Section 406.13.

7) DS Sec.2-02.2.1.A.12: Revise the grading plan to verify the minimum width opening for the proposed sidewalk and gate located along the south side of the building. All gates and sidewalks must meet the minimum width requirements per ANSI Standards A117.1-2003.

8) DS Sec.2-02.2.1.A.12: Revise the grading plan to show that all proposed handicap access ramps meet the design requirements per ANSI Standards A117.1-2003 Section 406.13. Provide details or keynotes that label truncated domes at all transitions from pedestrian circulation to vehicular circulation. Specifically for the proposed ramp at the handicap parking spaces to the adjacent sidewalk. If the striped area is the ramp the truncated domes must be provided along the bottom of the ramp not the top. Provide the ramp slopes (Longitudinal and cross slopes) to verify conformance with ANSI.

9) Revise Detail #9 on Sheet C1.2 to provide the elevations, minimum slopes and other construction details for the proposed handicap access ramp. Truncated domes are required along the bottom of the ramp at the transition of pedestrian circulation to vehicular circulation. If the striped area is not acting as the ramp then revise the detail to provide the 5-foot landing at the top of the ramp at the transition of the sidewalk.

10) Revise Detail #4 on Sheet C1.2 to dimension the minimum 6-inch reveal that is required from the top of the sidewalk to the top of the finished grade of asphalt or concrete.

11) DS Sec.10-02.2.3.1.6.4.a: Revise the grading plan to show all wall openings, Keynote #38, along the proposed CMU wall located in the northwest corner of the site. Wall openings are required along with spot elevations to clearly show that stormwater from the vehicular use area drains into the proposed water harvesting area.

12) DS Sec.3-01.5.1.A.1: Revise the grading plan to clearly show that the proposed 5-foot high CMU wall does not encroach into the sight visibility triangles. Line of sight shall not be obscured between 30-inches and 6-feet through the triangle area adjacent to the driveway. Make the dimensions in plan view more clear for building purposes that the wall portion located within the SVT area will be less than 30-inches.

13) DS Sec.11-01.4.1.C.3: Revise the grading plan to provide spot elevation for all proposed sewer clean out locations. Provide the pipe diameter and the invert and rim elevations of all clean outs in plan view for grading purposes.

14) DS Sec.11-01: Provide general grading note, including a grading/drainage note specifying conformance with City of Tucson Development Standard 11-01.0 (excavation and grading requirements).

15) DS Sec.11-01.4.1.C.4: Provide a General Note stating that all fencing and walls will require a separate permit for review and approval by all necessary Development Services Departments.

16) Provide a general note on the grading plan to state the following: "Call for a Pre-construction meeting prior to start of earthwork. To schedule a DSD Pre-construction meeting, SWPPP inspection or general Engineering Inspections, call IVR (740-6970), or schedule with a Customer Service Representative at the Development Services Department, or contact DSD Engineering at 791-5550 extension 2101, or schedule inspections online at: http://www.ci.tucson.az.us/dsd/Online_Services/Online_Permits/online_permits.html

17) Approval from TDOT Permits and Codes for all improvements within the public right-of-way will be required. A right-of-way use permit application will be required prior to construction. Contact Thad Harvison, (520)-791-5100 or Thad.Harvison@tucsonaz.gov for all right-of-way requirements and permit applications.

18) Please ensure that any future grading plan will be consistent with the site plan and Drainage Statement. Grading standards may be accessed at: http://www.ci.tucson.az.us/dsd/DevStandsTOC.pdf


GENERAL COMMENTS:

Please provide a revised grading plan that addresses the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments. Enclose "redlines" with the resubmittal package.

Further comments may be generated upon resubmittal of the grading plan review.

If you have any questions, or to schedule an appointment, I can be reached at 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services
01/07/2008 ANDREW CONNOR NPPO REVIEW Denied Submit a copy of the approved landscape plan for reference. The grading application will be reviewed for compliance when the approved document is included in the submittal.
02/01/2008 MICHAEL ST. PAUL ZONING REVIEW Denied February 1, 2008

Development Services Department
Zoning Review Section

Michael St.Paul
Planning Technician

T07BU02627 Grading Plans for T07CM03094 (Approved)
1044 North Jerrie Avenue

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. If revisions to the site and landscape plans are required due to grading requirements, please submit those plans for revision. Please submit two copies of the most resent approved and stamped Site Plan, Landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the approved development plan. Additional comments may be forthcoming.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/12/2008 CINDY AGUILAR OUT TO CUSTOMER Completed