Permit Number: T07BU02609
Parcel: 11004343C

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T07BU02609
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2008 LOREN MAKUS ENGINEERING REVIEW Approved February 28, 2008
T07BU02609
Grading Plan Review
Loren Makus, EIT

Grading Plan Comments:

1. As previously commented: provide details of the water harvesting basins and representative proposed spot elevations to demonstrate that the basins will be approximately level and maximize ponding. Although the plan specifies that the water harvesting basins will have flat bottoms, the spot grades near the basins indicate that the basin bottoms will be nearly 2.5 feet below the adjacent ground in some areas. Provide sufficient specific details for each microbasin area to show how the basin will be constructed safely and clearly address the slope surface treatment for these areas.
2. Provide representative cross sections across the project area, showing grades and surface details. Provide sections on each axis.
3. Microbasin B is show immediately adjacent to the proposed structure. Provide a geotechnical engineering report addressing the effect of the water harvesting area on the soil and foundation of the structure.
4. Show paved access with sufficient maneuverability for the dumpster enclosure. Is a dumpster enclosure appropriate for a residential development?
5. Clearly identify the grading limits for the project.
6. Provide a clear description of the proposed new fence and gates. Provide specifications and details including length, height and material.
SWPPP comments
7. The SWPPP clearly indicates that this project is for the construction of a museum. The grading plan indicates that it is for a residence. The plans must be consistent.
02/29/2008 ANDREW CONNOR NPPO REVIEW Denied Submit a copy of the approved development plan including landscape and native plant preservation plans for reference. The grading application will be reviewed for compliance when the approved documents are included in the submittal.
03/21/2008 MICHAEL ST. PAUL ZONING REVIEW Denied March 21, 2008

Development Services Department
Zoning Review Section

Michael St.Paul
Planning Technician

T07BU02609 Grading Plans for D07-0026
Address: 4415 East Fort Lowell Road

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. In addition, we could not verify that the grading plan was in compliance with the approved development plan for Zoning Review. Please submit two copies of the approved and stamped Development Plan/Site Plan, Landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the approved development plan. Additional comments may be forthcoming.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/25/2008 SUE REEVES OUT TO CUSTOMER Completed