Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - GRADING ALL
Permit Number - T07BU02580
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/23/2008 | DAVID RIVERA | ZONING | REVIEW | Denied | Until the site plan is approved by all divisions, and engineering and landscape approve the grading plan, zoning is unable to approve the grading plans. I will continue the review once the above is finished. If possible, I will review it at the counter if you email me for an appointment at Heather.Thrall@tucsonaz.gov and specify that you're requesting an appointment for this project. Thank you. |
05/28/2008 | ANDREW CONNOR | NPPO | REVIEW | Denied | Site plan approval is necessary to continue review. |
06/23/2008 | JASON GREEN | ENGINEERING | REVIEW | Denied | DATE: June 23, 2008 SUBJECT: 1300 N Greasewood Road Grading Plan- 3rd Engineering Review TO: Grenier Engineering, ATTN: Kent Delph, P.E. LOCATION: T14S R13E Sec04 Ward 1 REVIEWERS: Jason Green, CFM ACTIVITY: T07BU02580 (Grading Plan) SUMMARY: Engineering Division of Development Services Department has received and reviewed the revised grading plan (T07BU02580), Drainage Report (Grenier Engineering, Inc., 10DEC07 revised 18MAR08, 15MAY08), Geotechnical Evaluation (Western Technology Inc., 27JUL07 Addendum 25FEB08) and Stormwater Pollution Prevention Plan (Grenier Engineering, Inc, 06MAR08, revised 20MAY08) for the above referenced property. Engineering Division does not recommend approval of the grading plan at this time. The following items need to be addressed: GRADING PLAN COMMENTS: 1) Provide a copy of an approved site plan (T07CM04673). The grading plan can not be approved until verification that all details, locations, dimensions, and plan profiles match the approved site plan. Verify all information associated with the site plan is shown on the grading plan that will be used as the construction document. 2) Revise cross section #4 on sheet 2 to calls out mitered ends for the proposed 12-inch CMP. This comment was not addressed from the last review. 3) DS Sec.3-05.2.2.D: Revise the grading plan to provide all dimensions for the existing back-up spurs with a minimum of 3-foot radii (provide keynote 1 from the curb radii table shown on Sheet 4). Refer to DS Sec.3-05.2.2.D for clarification. 4) Please ensure that any future grading plan will be consistent with the site plan, Drainage Report and geotechnical report. Grading standards may be accessed at: http://www.ci.tucson.az.us/dsd/DevStandsTOC.pdf STORMWATER POLLUTION PREVENTION PLAN: The submitted SWPPP report meets the requirements of the AZPDES Construction General Permit (CGP). Provide 3 copies of the SWPPP Report and exhibits with the resubmittal for stamped approval. GENERAL COMMENTS: Please provide a revised grading plan that addresses the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments. Enclose "redlines," Drainage Report, geotechnical evaluation and 3 copies of the SWPPP with the resubmittal package. Further comments may be generated upon resubmittal of the grading plan review. If you have any questions or to schedule an appointment I can be reached at 837-4929. Jason Green, CFM Senior Engineer Associate Engineering Division COT Development Services |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/23/2008 | VFLORES1 | OUT TO CUSTOMER | Completed |
06/23/2008 | SUE REEVES | REJECT SHELF | Completed |