Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07BU02413
Parcel: Unknown

Address:
4328 N ORACLE RD

Review Status: Completed

Review Details: REVISION - GRADING

Permit Number - T07BU02413
Review Name: REVISION - GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/14/2008 WILLDAN ENGINEERING REVIEW Approved
05/14/2008 STEVE SHIELDS ZONING REVIEW Approved
05/16/2008 JOE LINVILLE NPPO REVIEW Denied 1) Section A/2 on the grading plan does not conform to the development plan indications of a 3:1 slope.

Basin slopes are required to have slopes no steeper than 4:1 where depths are three feet or greater. SDRM, DS 10-01.4 (P.78). (The depth is measured from the top of the slope at the lowest point on the basin rim to the toe of slope at the lowest point in the basin.) Revise where applicable.

Alternatively, retaining walls (as indicated on the previous version) are acceptable for up to 35% of the basin perimeter per P. 79 of SDRM.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/19/2008 CINDY AGUILAR OUT TO CUSTOMER Completed
05/19/2008 SHANAE POWELL REJECT SHELF Completed