Permit Number: T07BU02413
Parcel: Unknown

Address:
4328 N ORACLE RD

Review Status: Completed

Review Details: RESUBMITTAL - GRADING

Permit Number - T07BU02413
Review Name: RESUBMITTAL - GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2008 MICHAEL ST. PAUL ZONING REVIEW Denied March 3, 2008

Development Services Department
Zoning Review Section

Michael St.Paul
Planning Technician

T07BU02413 Grading Plans for D06-0014
4328 North Oracle Road

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. The Development Plan has been revised but the revisions have been denied. Therefore, we could not verify that the grading plan was in compliance with the approved development plan for Zoning Review. Please submit two copies of the approved and stamped Development Plan, Landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the approved development plan. Additional comments may be forthcoming.


Previous Comments:

DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Corner Retail - Lot 9
T07BU02413
Grading Plan (1st Review)

TRANSMITTAL DATE: January 23, 2008

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Parking area island located east of Bldg. 12 does not match what is shown on the approved development plan.

3. Pedestrian access/accessible route shown between Bldg 12 & Bldg 13 does not match what is shown on the approved development plan.

4. Pedestrian access/accessible route shown near the southeast corner of Bldg 10 does not match what is shown on the approved development plan.

5. The loading zone and refuse enclosure setup, located along the east side of Bldg 10 will not work as shown and does not match the approved development plan.

6. The refuse enclosure located along the east side of Bldg 9 does not match the approved development plan.

7. The curb ramp setup and sidewalk located on the east side of the entrance PAAL off of Wetmore Road does not match the approved development plan.

8. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t07bu02413

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approved site plans and additional requested documents