Permit Number: T07BU02314
Parcel: 11107331C

Address:
2645 N EDITH BL

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T07BU02314
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2008 ANDREW CONNOR NPPO REVIEW Passed
01/23/2008 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: January 23, 2008
SUBJECT: New Duplex
TO: Joe Barbea
LOCATION: 2645 N Edith Blvd, T13S R14E Sec33, Ward 3
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T07BU02314 (Second Review)


RESUBMITTAL REQUIRED: Grading Plan

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed grading plan for the above referenced property. Engineering Division does not recommend approval of the grading plan at this time. Please address the following review comments prior to the next submittal.


Grading Plan:
1. Attach response letter to the comments along with the corrected copies of the Grading Plan.
2. Complied
3. Complied
4. Complied
5. Complied
6. Complied.
7. Complied
8. Complied
9. Complied
10. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
11. Complied
12. Complied
13. Complied
14. Complied
15. Cut or fill slopes require a 2' minimum setback from property line. Provide detail of cross section across property and indicate 2' setback. Grading plan indicates estimated cut and fill quantities. Show where the grading is going to be taking place and provide existing and proposed grades clearly labeled on grading plan.
16. Complied
17. Complied
18. N/A
19. Complied
20. Provide existing and future site visibility triangles. Modify alignment of SVT to depict actual alignment.
21. Complied
22. Complied
23. Complied
24. Complied
25. Complied
26. Complied
27. Site plan is currently in review. Any changes made to the Site Plan must be reflected on the Grading Plan. The Site Plan and the Grading Plan must match.
28. Additional comments may be forthcoming on resubmittal, depending on the nature and extent of the revisions that occur to the plans.

If you have any questions, I can be reached at 791-5550 x1193 or Bianca.Ramirez@tucsonaz.gov
Bianca Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928
(520) 879-8010 fax
02/01/2008 MICHAEL ST. PAUL ZONING REVIEW Denied February 1, 2008

Development Services Department
Zoning Review Section

Michael St.Paul
Planning Technician

T07BU02314 Grading Plans for T07CM03342
2645 East Edith Blvd.

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering Section and until all zoning comments or concerns have been addressed.

2. In addition, we could not verify that the grading plan was in compliance with a site plan for this site approved by Zoning Review. Please submit two copies of the approved and stamped Site Plan.

3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the approved development plan. Additional comments may be forthcoming.