11/29/2007 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: November 28, 2007
SUBJECT: New Duplex
TO: Joe Barbea
LOCATION: 2645 N Edith Blvd, T13S R14E Sec33, Ward 3
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T07BU02314 (First Review)


RESUBMITTAL REQUIRED: Grading Plan

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed grading plan for the above referenced property. Engineering Division does not recommend approval of the grading plan at this time. Please address the following review comments prior to the next submittal.


Grading Plan:
1. Attach response letter to the comments along with the corrected copies of the Grading Plan.
2. Add note: "Depress all landscaped areas a maximum of 6" for water harvesting"
3. Add the following notes to the grading plan notes:
ยท "The approved Grading Plan is the only acceptable construction plan onsite. The Contractor may not use any other plans, such as the approved Tentative Plat and/or Development Plan, for construction purposes. The Contractor may ask the Development Services Inspector to consult with the other approved plans for additional information or details that might not be included on the approved grading plan but needed for completion of work."
4. Provide section corners within Location Map
5. Show cross-section with transverse and longitudinal slopes.
6. Show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4.
7. Call out surface paving material. Remove shading from plan for microfilming purposes.
8. Curb and Gutter elevation include drainage flow with percent slope.
9. Show details of all surface materials.
10. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
11. Indicate Note: The entire property lies within a City of Tucson regulatory floor hazard area.
12. Indicate Note: The water surface elevation is 2419.8 per Datum NAVD 1988
13. Indicate Note: This development contains a requirement that the applicants authorized representative complete an elevation certificate and is returned to the Development Services Department (DSD) Engineering Division prior to approval of the pre slab inspection and the final inspection both of the original elevation certificate must be returned to the DSD Engineering Division.
14. Call out the name of all wash - Christmas Wash Floodplain.
15. Cut or fill slopes require a 2' minimum setback from property line. Provide detail of cross section across property and indicate 2' setback.
16. Drainage patterns with percent slopes (Show patterns within the first 100 feet from the property line).
17. Flow arrows, grades and flow rates within and adjacent to site to show drainage scheme.
18. Call out peak discharges entering and exiting the site.
19. Provide property description on grading plan.
20. Provide existing and future site visibility triangles.
21. Dimension the radius of back up spur located in southwest corner of parking area. It must be clear on the plan that the back up spur had 3' radius.
22. Label existing and future right of way dimensions.
23. Dimension from centerline to existing and proposed curbs, sidewalks, driveways and utility lines.
24. Provide recordation information for each of the streets indicated, including book and page.
25. Provide Benchmark based on City of Tucson Datum, including City Field Book and Page Number.
26. 5' sidewalk required along Edith Blvd.
27. Site plan is currently in review. Any changes made to the Site Plan must be reflected on the Grading Plan. The Site Plan and the Grading Plan must match.
28. Additional comments may be forthcoming on resubmittal, depending on the nature and extent of the revisions that occur to the plans.

If you have any questions, I can be reached at 791-5550 x1193 or Bianca.Ramirez@tucsonaz.gov
Bianca Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928
(520) 879-8010 fax
11/30/2007 MICHAEL ST. PAUL ZONING REVIEW Denied November 30, 2007

Development Services Department
Zoning Review Section

Michael St.Paul
Planning Technician

T07BU02314 Grading Plans for T07CM03342
2645 East Edith Blvd.

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. In addition, we could not verify that the grading plan was in compliance with a site plan for this site approved by Zoning Review. Please submit two copies of the approved and stamped Site Plan, Landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the approved development plan. Additional comments may be forthcoming.
12/10/2007 ANDREW CONNOR NPPO REVIEW Denied Needs NPPO site review / New lot split 2007.

Site plan approval is necessary to continue review.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/28/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
12/28/2007 GERARDO BONILLA REJECT SHELF Completed