Permit Number: T07BU02282
Parcel: 11103181E

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T07BU02282
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/30/2008 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: January 30, 2008
SUBJECT: Grading Plan
TO: Fast Permits
LOCATION: 3320 N Country Club, T13S, R14E, Section 36, Ward 28
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T07BU02282 (Third Review)


RESUBMITTAL REQUIRED: Grading Plan

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed grading plan for the above referenced property. Engineering Division does not recommend approval of the grading plan at this time. Please address the following review comments prior to the next submittal.


Grading Plan:
1. Include a response letter to the comments along with the corrected copies of the Grading Plan.
2. Complied
3. Complied
4. Complied
5. Complied
6. Complied
7. Complied
8. Complied
9. Complied
10. Complied
11. Complied
12. Complied
13. Complied
14. Complied
15. Complied
16. Complied
17. Complied
18. Complied
19. Complied
20. Complied
21. Complied
22. Complied
23. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
24. Complied
25. Complied
27. 5' sidewalk required for pedestrian access around building. Clearly indicate that pedestrian access has been provided. Provide on grading plan.
28. Complied
29. Per grading plan sidewalk adjacent to parking appears to be flush with pavement. Truncated domes required along areas where pedestrian circulation area and vehicular areas are adjacent.
30. Remove trash enclosure detail located on sheet 2 of 3.
31. Additional comments may be forthcoming.

Note that the purpose of the grading plan is for inspectors to utilize the plans during their inspection. Specific plan information is needed to ensure that the inspector has the adequate information they need to provide the inspection. The grading plan and site plans are often separated on a construction project and therefore, both need to have the information required for the inspector to complete the inspection.

If you have any questions, I can be reached at 837-4928 or Bianca. Ramirez@tucsonaz.gov
Bianca Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837 - 4928 office
(520) 879 - 8010 fax
02/15/2008 MICHAEL ST. PAUL ZONING REVIEW Denied February 15, 2008

Development Services Department
Zoning Review Section

Michael St.Paul
Planning Technician

T07BU02282 Grading Plans for T07CM02466
3320 North Country Club Road

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. It appears that the grading plan matches the site plan and that all comments for Zoning Review have been successfully addressed.

3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the approved development plan. Additional comments may be forthcoming.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/19/2008 GERARDO BONILLA OUT TO CUSTOMER Completed