Permit Number: T07BU02282
Parcel: 11103181E

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T07BU02282
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2008 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: January 4, 2007
SUBJECT: Grading Plan
TO: Fast Permits
LOCATION: 3320 N Country Club, T13S, R14E, Section 36, Ward 28
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T07BU02282 (Second Review)


RESUBMITTAL REQUIRED: Grading Plan

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed grading plan for the above referenced property. Engineering Division does not recommend approval of the grading plan at this time. Please address the following review comments prior to the next submittal.


Grading Plan:
1. Include a response letter to the comments along with the corrected copies of the Grading Plan.
2. Complied
3. Complied
4. Complied
5. Complied
6. Complied
7. Site visibility triangles are to start at edge of curb and back 20'. Per plan minimum 20' setback does not appear to be met.
8. Complied
9. Complied
10. Provide site plan and grading plan activity numbers on the lower right hand corner of each sheet. Provide the activities numbers on sheet 2 and 3.
11. Location map shows NTS and also indicates 3" = 1 mile. Location map is to be at a scale of 3" = 1 mile.
12. Complied
13. Indicate on grading plan Cut = 0 Cubic Yards.
14. Dimension Right of way and label existing and future right of way. Existing right of way appears to be 60' - 49' and the future right of way appears to be 100'.
15. Complied
16. Provide labels for dimensions from street monument lines to existing and proposed curbs, sidewalks, driveways and utility lines.
17. Provide benchmark based on City of Tucson Datum, Including City Field Book and page number.
18. Complied
19. Complied
20. Complied
21. On sheet 1, clarify types of scuppers and provide detail in detail B. If scupper is roof scupper clearly indicate by labeling as such.
22. Complied
23. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
24. Placement of fill in excess of 2' above existing grade at any location in the outer 100' of the developing site is not allowed and/or shall meet the requirements per D.S. 11-01. Provide zoning designation for adjacent properties. Be advised that there may be differential grading requirements based on what has been shown on plans. For N Country Club Rd and Cardi Blvd provide zoning across the street.
25. Drainage patterns with percent slopes and use arrows to indicate direction of slope. Ponding may be a concern. Clearly indicate that water will not be ponding in parking areas 17, 18 and 19. Depressed curbs may be considered to allow any water to enter adjacent landscape area.
26. Provide rates within and adjacent to site to show drainage scheme. Call out peak discharges entering and exiting the site on the site plan and in the location of the called out discharge.
27. 5' sidewalk required for pedestrian access around building. Clearly indicate that pedestrian access has been provided.
28. Verify that all text in a minimum of 12-point font for recordation purposes.
29. Per grading plan sidewalk adjacent to parking appears to be flush with pavement. Truncated domes required along areas where pedestrian circulation area and vehicular areas are adjacent.
30. Additional comments may be forthcoming.

Note that the purpose of the grading plan is for inspectors to utilize the plans during their inspection. Specific plan information is needed to ensure that the inspector has the adequate information they need to provide the inspection. The grading plan and site plans are often separated on a construction project and therefore, both need to have the information required for the inspector to complete the inspection.

If you have any questions, I can be reached at 837-4928 or Bianca. Ramirez@tucsonaz.gov
Bianca Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837 - 4928 office
(520) 879 - 8010 fax
12/12/2007 MICHAEL ST. PAUL ZONING REVIEW Denied December 12, 2007

Development Services Department
Zoning Review Section

Michael St.Paul
Planning Technician

T07BU02282 Grading Plans for T07CM02466
3320 North Country Club Road

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. It appears that the grading plan matches the site plan and that all comments for Zoning Review have been successfully addressed.

3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the approved development plan. Additional comments may be forthcoming.
12/17/2007 ANDREW CONNOR NPPO REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/10/2008 THAUSER1 OUT TO CUSTOMER Completed
01/10/2008 SHANAE POWELL REJECT SHELF Completed