Permit Review Detail
Review Status: Completed
Review Details: GRADING
Permit Number - T07BU02273
Review Name: GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/07/2007 | DAVID RIVERA | ZONING | REVIEW | Denied | Development Services Department Zoning Review Section 11/07/07 David Rivera Principal Planner Comments: 1. The grading plan has been reviewed by Zoning Section comments or concerns have been addressed. 2. Zoning could not verify that the grading plan was in compliance with the approved site plan. Please submit two copies of the DSD approved and stamped site, landscape, and NPPO plans with the next grading plan submittal. 3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the approved and stamped site plan. Additional comments may be forthcoming. 4. Zoning is willing to review and approve the grading plan (if possible) over the counter once the CDRC approved and stamped development plan is included with the next grading plan submittal. Please call in advance for an appointment if this is an option you would like to pursue. Phone 791-5608 ext. 74957 |
| 11/13/2007 | ANDREW CONNOR | NPPO | REVIEW | Denied | Site plan approval is necessary to continue review. |
| 12/03/2007 | JASON GREEN | ENGINEERING | REVIEW | Denied | DATE: December 5, 2007 SUBJECT: 3535 E Valencia Road- Engineering Review New Parking Lot Expansion TO: Metro Permits Express Attn: Lisa Bowers LOCATION: T15S R14E Sec09 Ward 5 REVIEWERS: Jason Green, CFM ACTIVITY: T07OT02454 (Site Plan) and T07BU02273 (Grading Plan) SUMMARY: Engineering Division of Development Services Department has received and reviewed the site plan (T07OT02454), grading plan (T07BU02273), Drainage Report (O'Neill Engineering, 26OCT07), and Stormwater Pollution Prevention Plan (O'Neill Engineering, 30OCT07) for the above referenced property. Engineering Division does not recommend approval of the site plan, grading plan or Stormwater Pollution Prevention Plan (SWPPP) at this time. The following items need to be addressed: SITE PLAN COMMENTS: 1) DS Sec.2-02.2.1.A.3: Provide the administrative or situs address on the site plan for the subject property. 2) DS Sec.2-02.2.1.A.4: Revise the location map to show the subject parcel location approximately centered within a one square mile area. Identify conditions within the square mile area shown on the project location map located on Sheet SP-1, such as major watercourses (Rodeo Wash) and the section corners. 3) DS Sec.2-02.2.1.A.8: Revise the site plan to show wheel stop barrier for the parking spaces located along any adjacent landscape areas, fencing and/or pedestrian circulation paths. The barriers are to be set at 15.5-feet to accommodate the required 2.5-foot overhang to prevent encroachment or damage to the proposed landscape area, fencing and the required pedestrian path. Verify the minimum 15.5-foot parking space dimension at the wheel stop locations shown at the landscape islands within the proposed parking lot. Verify the 2.5-foot overhang along the north property line at the parking space location and proposed wrought iron fence. 4) DS Sec.2-02.2.1.A.8: Revise the site plan to remove the existing wrought iron fence from the proposed Parking Area Access Lane (PAAL) entry points located along the southern portion of the proposed parking lot. Dimension the PAAL entries to verify the 24-foot requirement. 5) DS Sec.2-02.2.1.A.11: Verify the PAAL width at the entry gates for the proposed PAAL. Verify that the gate meets the minimum 12-foot opening on both sides of the access aisle, or 20-feet if fire requires access for fire vehicles. 6) DS Sec.2-02.2.1.A.11: Depict and label the 18-feet radii concrete curb returns per City of Tucson/Pima County Standard Detail 213 (PC/COT SD 213 and the Transportation Access Management Guidelines (TAMG) at the proposed driveway entrances located on Brittania Drive. The curbs should be constructed at the edge of pavement, which must also be depicted on the site plan. Curb returns must be constructed entirely within the subject parcel refer to DS Sec.3-01.3.2.C for street development standards. 7) DS Sec.2-02.2.1.A.12: Verify the 5-foot requirement for the pedestrian circulation path between the existing PAAL and the existing wrought iron fence that connects Brittania Drive to the existing building. The wrought iron fence is not included on the last approved site plan and per the proposed site plan the minimum 5-foot requirement does not appear to be met. 8) DS Sec.2-02.2.1.A.12: Clarify the need for the proposed crosswalk location along the new entry PAAL. Since sidewalks are not proposed it seems that crosswalks would not be needed, clarify. 9) DS Sec.2-02.2.1.A.12: Revise the site plan to show that all proposed and revised handicap access ramps meet the design requirements per ANSI Standards A117.1-2003 Section 406.13. Provide details or keynotes that label truncated domes at all transitions from pedestrian circulation to vehicular circulation. 10) DS Sec.2-02.2.1.A.16: Revise the site plan to label and dimension the proposed stormwater grate and pipe located in the northwest corner of the vehicular use area. 11) DS Sec.2-02.2.1.A.16: Revise the site plan to label the existing grate, storm drain pipe and rock riprap as to be removed. Per the civil sheets these storm drain improvements are to be replaced. 12) DS Sec.2-02.2.1.A.16: Revise the site plan to label all rock riprap that is shown in the proposed vehicular use area as to be removed. Rock riprap can not interfere with vehicular circulation as shown on the proposed site plan. 13) DS Sec.2-02.2.1.A.17: Provide estimated cut and fill quantities on the site plan for grading plan purposes. 14) DS Sec.2-02.2.1.A.20: Clarify the new easements that are shown on the proposed site plan. Provide recordation information for all easements that are shown specifically the 15-foot water line easement and the 10-foot electric line easement. 15) DS Sec.2-02.2.1.A.27: Provide approval for the existing wrought iron fence that is shown on the proposed site plan, per the last approved site plan a wrought iron fence is not included. All fencing, existing or proposed, will require a separate review and approval from all Development Services Departments. Fencing must be constructed entirely on the subject property unless an easement is granted for the maintenance and construction of the proposed and existing fence. 16) DS Sec.2-02.2.1.A.32: Clarify the relocation of the refuse containers as shown on the proposed site plan. Per the last approved site plan the refuse containers have been moved from what was approved. A new review and detail of the refuse container is required with the relocation to verify that all requirements within DS Sec.6-01 have been met. 17) DS Sec.2-02.2.1.A.32: Provide a detail on both the Architect site plan and Civil grading plan sheets showing the dimensions for refuse container. Provide the minimum dimensions for the enclosure that meets or exceeds the standards within the attached Figure 3 per DS Sec.6-01 for the required refuse enclosure construction. GRADING PLAN: The project was reviewed for grading plan purposes, however until all site plan and Drainage Report comments are addressed the grading plan could not be shown to be in conformance with an approved plan. 18) Revise Sheet C-1 to provide estimated cut and fill quantities on the grading plan as indicated. 19) DS Sec.6-01: Provide a detail on the Civil grading plan sheets showing the dimensions for refuse container. Provide the minimum dimensions for the enclosure that meets or exceeds the standards within the attached Figure 3 per DS Sec.6-01 for the required refuse enclosure construction. 20) Revise sheet C-3 on the grading plan to show wheel stop barrier for the parking spaces located along any adjacent landscape areas and/or pedestrian circulation paths. The barriers are to be set at 15.5-feet to accommodate the required 2.5-foot overhang to prevent encroachment or damage to the proposed landscape area and the required clear 4-foot pedestrian path. Verify the minimum 15.5-foot parking space dimension at the wheel stop locations shown at the landscape islands within the proposed parking lot. Verify the 2.5-foot overhang along the north property line at the parking space location and proposed wrought iron fence. 21) DS Sec.3-01.3.2.C: Depict and label the 18-feet radii concrete curb returns per City of Tucson/Pima County Standard Detail 213 (PC/COT SD 213 and the Transportation Access Management Guidelines (TAMG) at the proposed driveway entrances located on Brittania Drive. The curbs should be constructed at the edge of pavement, which must also be depicted on the grading plan. Curb returns must be constructed entirely within the subject parcel refer to DS Sec.3-01.3.2.C for street development standards. 22) Revise the grading plan or Keynote #3 to show that all proposed and revised handicap access ramps meet the design requirements per ANSI Standards A117.1-2003 Section 406.13. Label the required truncated domes at all transitions from pedestrian circulation to vehicular circulation. 23) Revise the grading plan to label all rock riprap that is shown in the proposed vehicular use area as to be removed. Rock riprap can not interfere with vehicular circulation as shown on the proposed grading plan. 24) DS Sec.11-01.4.1.C.4: Provide a General Note stating that all fencing and walls will require a separate permit for review and approval by all necessary Development Services Departments. Provide approval for the existing wrought iron fence that is shown on the proposed grading plan, per the last approved site plan a wrought iron fence is not included. All fencing, existing or proposed, will require a separate review and approval from all Development Services Departments. Fencing must be constructed entirely on the subject property unless an easement is granted for the maintenance and construction of the proposed and existing fence. 25) Provide a general note on the grading plan to state the following; "Call for a Pre-construction meeting prior to start of earthwork. To schedule a DSD Pre-construction meeting, SWPPP inspection or general Engineering Inspections, call IVR (740-6970), or schedule with a Customer Service Representative at the Development Services Department, or contact DSD Engineering at 791-5550 extension 2101, or schedule inspections online at: http://www.ci.tucson.az.us/dsd/Online_Services/Online_Permits/online_permits.html 26) DS Sec.11-01: Provide general grading notes, including a grading/drainage note specifying conformance with City of Tucson Development Standard 11-01.0 (excavation and grading requirements). DRAINAGE REPORT: 27) DS Sec.10-02.10.9.1: Revise the drainage report to include a discussion and calculations for the proposed revised grate and storm drain location. The master drainage report does not include a discussion on a storm drain that is connected to the public storm drain system. Very the onsite flows for the new parking lot and that the proposed grate and storm drain meets the minimum requirements so that stormwater does not pond within the vehicular use area at a depth of great than 1 foot. GEOTECHNICAL REPORT: 28) DS Sec.10-01.III.3.5.1.3.a, 10-02.14.2.6: Provide the referenced Geotechnical Report Evaluation (Site General Notes B and C) that addresses the minimum following requirements: a) Soils report should provide a discussion of the potential for hydro-collapsible soils. b) The soils report shall provide identification / assessment of any potentially hazardous geotechnical areas, and state any geotechnical recommendations and whether there are special provisions for the soil preparation for this development. c) Provide pavement structure design for the vehicular use area. STORMWATER POLLUTION PREVENTION PLAN: The SWPPP does not meet the minimum requirements of the AzPDES Construction General Permit (CGP). 29) Part IV.C.2.a: Describe the project and its intended use after NOT is filed. 30) Part IV.C.3.c: Revise Sheet SW-2 on the map to correctly show the temporary silt fence control around the proposed waste disposal area. Per the exhibit the silt fence cuts right through this area, clarify. 31) Part IV.D.4.c: Provide the forms and checklists used for keeping the required inspection data. 32) Part IV.F: Include copies of the AZPDES permit (AZG2003-001) and signed NOI as part of the SWPPP submittal. NOI must be signed prior to SWPPP approval. 33) Part IV.J.2: Describe how and where the operator will post a sign at main entrance to site containing: AZPDES authorization number (or copy of NOI authorization), construction site contact name and telephone number, brief project description, location of SWPPP if the site is inactive or does not have an on-site storage location. 34) Tucson Code 26-42.b: The SWPPP report must be signed and sealed by the engineer of record. GENERAL COMMENTS: Please provide a revised site plan, drainage report, geotechnical engineering report, and a SWPPP that address the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments. Further comments may be generated upon resubmittal of the site plan, drainage report, geotechnical report, and SWPPP reviews. If you have any questions, or to schedule an appointment, I can be reached at 837-4929. Jason Green, CFM Senior Engineer Associate Engineering Division Development Services |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/05/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 12/05/2007 | SUE REEVES | REJECT SHELF | Completed |