Permit Number: T07BU02166
Parcel: 11516024C

Address:
2201 N FORBES BL

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T07BU02166
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. SOIL BEARING NOTE 7 ON S1 DISAGREES WITH STRUCTURAL CALCULATIONS NOTE INDICATING 1000 PSF.
2. 'LATERAL ANALYSIS' INDICATES 3 LEVELS @ 4500 #/LEVEL (PAGE 10), NOT ACTUAL DESIGN.
3. 'LATERAL ANALYSIS' INDICATES 3 LEVELS @ 5000 #/LEVEL (PAGE 40), NOT ACTUAL DESIGN.
4. CALCULATIONS FOR ADEQUACY OF CONCRETE SLAB UNDER NEW PALLET LOADS ARE MISSING.
5. CALCULATIONS FOR ADEQUACY OF SOIL UNDER NEW PALLET LOADS ARE MISSING.
11/15/2007 DAVE MANN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/21/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
11/21/2007 GERARDO BONILLA REJECT SHELF Completed