Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07BU02048
Parcel: 116022370

Review Status: Completed

Review Details: WALLS

Permit Number - T07BU02048
Review Name: WALLS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/26/2007 MICHAEL ST. PAUL ZONING REVIEW Approved
09/26/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved
09/26/2007 MICHAEL ST. PAUL NPPO REVIEW Passed
10/08/2007 RBROOKS1 BUILDING-COMMERCIAL REVIEW Approved 1. IN THE CACULATIONS IT IS NOTED THAT THE ASSUMED SOILS BEARING PRESSURE IS 15OO. THE CALCULATIONS APPEAR TO USE A SOIL BEARING PRESSURE OF 2000. PLEASE CLARIFY.

2. THE CALCULATIONS APPEAR TO SPECIFY THE RETIANING PORTION OF THE WALL TO HAVE #4 VERTICAL REINFORCING AT 24" O/C AND REINFORCING FOR THE FENCE PORTION OF THE WALL USING #4 @ 48" O/C. HOWEVER THE PLANS ILLUSTRATE AND SPECIFY THE VERTICAL REINFORCING FOR THE FENCE @32" O/C. WITH THIS THE FENCE REINFORCING WILL NOT CORRESPOND TO THE RETAINING FRINFORCING. PLEASE CLARIFY.