Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T07BU01974
Parcel: 134030380

Address:
8820 E 21ST ST

Review Status: Active

Review Details: RESUBMITTAL - GRADING

Permit Number - T07BU01974
Review Name: RESUBMITTAL - GRADING
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
03/31/2008 ANDREW CONNOR NPPO REVIEW Approv-Cond

Final Status

Task End Date Reviewer's Name Type of Review Description
03/31/2008 SUE REEVES APPROVAL SHELF RECEIVED