Review Details: RESUBMITTAL - GRADING ALL
Permit Number - T07BU01810
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/20/2008 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 06/27/2008 | LOREN MAKUS | ENGINEERING | REVIEW | Denied | July 1, 2008 T07BU01810 Grading Plan Review The previous comments have been addressed and the grading plan, drainage report and geotechnical report are accepted as submitted. However, since this project was reviewed the last time, a new construction general permit was issued by the State of Arizona, Department of Environmental Quality. Revise the SWPPP to be consistent with the construction general permit. Please obtain the SWPPP checklist from ADEQ and submit a completed checklist along with the revised SWPPP. Indicate in the checklist specifically how and where each checklist item has been addressed. Also provide an updated authorization from ADEQ. If you have any questions or wish to set up a meeting, please contact me at loren.makus@tucsonaz.gov or at 520.837.4927. Loren Makus, EIT Senior Engineering Associate |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/01/2008 | GERARDO BONILLA | REJECT SHELF | RECEIVED |