Review Details: GRADING

Permit Number - T07BU01775
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/13/2007 ANDREW CONNOR NPPO REVIEW Denied Submit a copy of the stamped approved site & landscape plans for reference. The grading application will be reviewed for compliance only when the approved documents are included in the submittal. Revise grading plans as necessary to comply with the approved site plan.
09/24/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: September 24, 2007
ACTIVITY NUMBER: T07BU01775
PROJECT NAME: El Sol Apartments
PROJECT ADDRESS: 2115 North Oracle Road
PROJECT REVIEWER: Patricia Gilbert

The following items must be revised or added to the grading plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: GRADING PLAN


1. A copy of the stamped approved Site Plan must be included with the Grading Plan submittal.

2. Provide the grading plan activity number on each sheet in the lower right hand corner.

3. Provide sight visibility triangles in the required locations.

4. Show roof drainage (flow arrows). DS 2-02.2.1.A.16.

5. Show the grading limits on the plan. See the Development Standard 11-01.9. for the required setbacks.

6. Show more finish grades on the plan. Drainage patterns must be readily definable in all areas. DS 2-02.2.1.A.16.

7. Add a general note; Call for a Pre-construction meeting prior to start of earthwork. To schedule a DSD Pre-construction meeting, SWPPP inspection or general Engineering Inspections, call IVR (740-6970), or schedule with a Customer Service Representative at the Development Services Department, or contact DSD Engineering at 791-5550 extension 2101, or schedule inspections online at: http://www.ci.tucson.az.us/dsd/Online_Services/Online_Permits/online_permits.html

8. Provide the area of disturbance.

9. Identify on sheet S-04 the abbreviations; FC, FP, HP.

10. On sheet S-04 provide the datum for the elevations.

11. There is a call out for type 2 scuppers with a leader arrow pointing to a symbol that appears to be a scupper. This symbol is provided in more than 30 locations on the site. It seems excessive to provide over 30 scuppers through out the site. Clarify and revise the site plan appropriately.

12. Provide the location of the roof/rain gutters and a detail.

13. Provide a cross section of the north, south, east and west boundary of the site. Provide dimensions, elevations and label appropriately.

14. Please note that subsequent comments may be necessary upon resubmittal, depending on the nature and extent of revisions that occur to the plans.
09/27/2007 DAVID RIVERA ZONING REVIEW Denied 09/27/07

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan on this review.

2. Zoning could not verify that the grading plan was in compliance with the DSD approved stamped site plan. Please include two copies of the DSD approved and stamped site, landscape, and NPPO plans with the next grading plan submittal.

3. Please ensure that the grading plan matches the DSD approved and stamped site plan.

4. Zoning will re-review the grading plan on the next submittal to ensure compliance with the DSD approved and stamped site plan. Additional comments may be forthcoming.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/15/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
10/15/2007 GERARDO BONILLA REJECT SHELF Completed