Permit Number: T07BU01747
Parcel: 13405118Q

Review Status: Completed

Review Details: GRADING

Permit Number - T07BU01747
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/28/2007 MICHAEL ST. PAUL ZONING REVIEW Denied August 28, 2007

Development Services Department
Zoning Review Section

Michael St.Paul
Planning Technician

T07BU01747 Grading Plans for D06-0003
1010 South Harrison Road

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. In addition, we could not verify that the grading plan was in compliance with the approved development plan for Zoning Review. Please submit two copies of the approved and stamped Development Plan/Site Plan, Landscape, and NPPO plans with the next grading plan submittal. Please be aware that the Development Plan must also go through the Site Plan process. This is a walk through process in which the stamped approved Development Plan is also approved as a Site Plan.

3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the approved development plan. Additional comments may be forthcoming.
08/31/2007 ANDREW CONNOR NPPO REVIEW Denied 1. Submit a copy of the approved development plan including landscape and NPPO plans for reference. Revise grading plans as necessary to comply with the approved plans.

2. The development plan must have a site card with DSD stamps and approvals from the appropriate divisions before the grading plan can be reviewed. Review will continue upon re-submittal of requested documents.
09/28/2007 PAUL MACHADO ENGINEERING REVIEW Denied To: Bruce Paton, P.E. DATE: October 15, 2007
Rick Engineering Company, Inc.
1745 E. River Road, Suite 101
Tucson, Arizona 85718

SUBJECT: Tutor Time Day Care, 1010 S. Harrison Road
Grading Plan T07BU01747 (First Review)
T14S, R15E, Section 15

RESUBMITTAL REQUIRED: Grading Plan, Drainage Report and SWPPP

The Grading Plan (GP) and Drainage Report (DR) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:
1. Please include a response letter to the comments along with the corrected copies of the GP.
2. Add the basin(s) maintenance responsibility note per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the GP.
3. List the Grading plan (T07BU01747) and the Site plan (T07CM03498) number on all sheets.
4. Show cross section with transverse and longitudinal slopes.
5. Curb and Gutter elevation include drainage flow with percent slope.
6. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
7. Show the 100-year flood peak discharge.
8. Cut or fill slopes require a 2' minimum setback from property line. Show on all details and cross-sections.
9. Drainage patterns with percent slopes (Show patterns within the first 100 feet from the property line).
10. Call out peak discharges entering and exiting the site.
11. Move the basin maint. ramp to the west in order for the service not to run over the rip-rap.
12. The door or access to the refuse enclosure on the detail, F/2, is shown on the opposite side of where it is shown on the plan view on sheet 3. Revise as necessary.
13. Resubmit 3 copies of the grading plan when all comments have been addressed.

Drainage report:
1. The DR has been accepted by engineering. However resubmit the reports along with the corrected copies of the grading plan.
Stormwater pollution prevention plan:
1. The SWPPP has been accepted by engineering. However resubmit the report along with the corrected copies of the grading plan.


If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:\1010 S. Harrison Rd Grad

Final Status

Task End Date Reviewer's Name Type of Review Description
10/22/2007 THAUSER1 OUT TO CUSTOMER Completed
10/22/2007 THAUSER1 REJECT SHELF Completed