Permit Number: T07BU01740
Parcel: 115180050

Address:
1601 N ORACLE RD

Review Status: Completed

Review Details: POOL:COMM-MODEL

Permit Number - T07BU01740
Review Name: POOL:COMM-MODEL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/17/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Approved
08/17/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
08/17/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a design for the semi-public spa by an Arizona Registrant per ANSI/NSPI-2 1999. Include an SVRS for each circulation pump.
08/17/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved
08/17/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07BU01740 8/1707

1. Provide an electrical design. Indicate tie-ins to equipment to be provided by others.
10/10/2007 VFLORES1 ZONING REVIEW Needs Review