Permit Number: T07BU01713
Parcel: 13326327E

Address:
145 N SARNOFF DR

Review Status: Active

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T07BU01713
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1) Please have a registrant complete the plans and seal them in accordance with the submittal requirements of the City of Tucson and section 106.1.1 of the 2006 IBC.

2) Please coordinate the information regarding the elevation difference and the ramp dimensions between the submittal sheets.

3) Please modify the height of the handrail per section 1012.2 of the 2006 IBC to 34" - 38".

4) Please verify if the ramp is intended to be accessible or not in compliance with ANSI 117.1-2003. The existing facility appears to already provide two accessible exits and therefore this exit does not have to be accessible. If it is intended to be accessible, please provide the requried manuevering clearance for the latch side approach on the pull side of the door per section 404.2.3 of ANSI 117.1-2003.

5) Please provide safety glazing in the window adjacent to the ramp in accordance with section 2406.3 of the 2006 IBC.

6) Please provide details for the handrail adjacent to the building in order to verify compliance with section 1012 of the 2006 IBC (i.e. offset distance, extensions, height, etc.).