Permit Number: T07BU01712
Parcel: 116300370

Review Status: Completed

Review Details: WALLS

Permit Number - T07BU01712
Review Name: WALLS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Approved 1) Please coordinate the top of wall information per section 106.1.1 of the 2006 IBC as a few of the top of wall elevations are listed as nearly 100' above the surrounding elevations.

2) Please specify on the plans the bottom of footing elevations and the construction details on the plans and coordinate the plan scale (listed as 1/4" = 1') per section 106.1.1 of the 2006 IBC.

3) Please coordinate the installation information regarding the installation of the geogrid with the specified locations of the pool, residence and site walls per section 106.1.1 of the 2006 IBC as the plans appear to indicate a conflice. In addition, please revise the structural calculations to include the surcharge from these adjacent structures and fixtures per 106.1.1 of the 2006 IBC as necessary.

4) Please specify the locations of all of the retaining walls, any site walls on top of retaining walls and any separate site walls over 6' per section 106.1.1 of the 2006 IBC.
09/27/2007 STEVE SHIELDS ZONING REVIEW Approved
09/27/2007 ELIZABETH EBERBACH ENGINEERING REVIEW Approved Reviewed ret walls at counter for setback. 256' total length. - EE
09/27/2007 PETER MCLAUGHLIN NPPO REVIEW Approved