Permit Review Detail
Review Status: Completed
Review Details: GRADING
Permit Number - T07BU01586
Review Name: GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/13/2007 | ANDREW CONNOR | NPPO | REVIEW | Denied | Submit a copy of the approved tentative plat including landscape and native plant preservation plans for reference. The grading application will be reviewed for compliance only when the approved documents are included in the submittal. Revise grading plans as necessary to comply with the approved tentative plat. |
| 08/21/2007 | MICHAEL ST. PAUL | ZONING | REVIEW | Denied | August 21, 2007 Development Services Department Zoning Review Section Michael St.Paul Planning Technician T07BU01586 Grading Plans for S05-187 Comments: 1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed. 2. Zoning could not verify that the grading plan was in compliance with the approved tentative plat. Please submit one copy of the CDRC approved and stamped tentative plat, landscape, and NPPO plans with the next grading plan submittal. 3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the CDRC approved and stamped tentative plat. Additional comments may be forthcoming. |
| 09/13/2007 | LOREN MAKUS | ENGINEERING | REVIEW | Denied | September 17, 2007 T07OT01586 Grading Plan Review for Copper Vista II Reviewer: Loren Makus, EIT Grading Plan Comments: 1. Show how each lot will be graded to provide drainage as indicated and to provide positive drainage from each structure. This can be done by providing typical lot drainage details or by providing lot grading information on the plan in some other way. 2. Confirm the described slopes for the basin detail on sheet 2. It appears that the Hs and Vs have been reversed. 3. Indicate by note or by providing spot grades, that the basin will be graded to drain toward the outlet. 4. Clarify how the driveways will be connected to Jeanette Boulevard. The plan view indicates that the driveways will be using aprons and that the existing curb will be maintained. 5. Clarify in the detail that the pipes from the catch basins to the retention/detention basin will be RCP as specified in the plan view. 6. Indicate that the pipe outlet will be cut to match the surface grade. SWPPP Comments 7. Part IV.B.2.c Explicitly indicate in the SWPPP the name of the operator with operational control over project specifications (including the ability to make modifications in specifications). 8. Part IV.B.2.c Explicitly indicate in the SWPPP the name of the operator with operational control over day-to-day activities at the construction site. 9. Part IV.F. Include copy of a signed NOI. 10. Revise the concrete washout paragraph (page 11) to provide for a concrete washout location in accordance with the aquifer protection program general permit. 11. Part IV.H.1. Indicate which of the inspection schedules will be used for this project. 12. Revise the detail for the silt fence to eliminate the placement of fill above the adjacent grade. Inspection experience indicates that fill above grade frequently contributes to silt fence failure. 13. Part IV.C.3.a. Identify on the map drainage patterns and estimated slopes after grading 14. Part IV.C.3.b. Identify on the map areas of soil disturbance Identify on the map areas not to be disturbed 15. Part IV.C.3.c. Identify on the map locations of structural and nonstructural controls identified in the SWPPP. 16. Part IV.C.3.d. Identify on the map locations where stabilization practices are expected to occur 17. Part IV.C.3.g. Identify on the map locations where stormwater is discharged to a surface water (e.g. ephemeral waters or dry washes) and to MS4s If you have any questions, I can be reached at 520.837.4927 or loren.makus@tucsonaz.gov. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/26/2007 | THAUSER1 | OUT TO CUSTOMER | Completed |
| 11/26/2007 | GERARDO BONILLA | REJECT SHELF | Completed |