Permit Number: T07BU01547
Parcel: 119310120

Review Status: Completed

Review Details: REVISION - GRADING

Permit Number - T07BU01547
Review Name: REVISION - GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/02/2010 DAVID RIVERA ZONING REVIEW Approved
09/08/2010 ELIZABETH EBERBACH ENGINEERING REVIEW Denied SUBJECT: 3007 W Via De Suenos HDZ Final Revised Grading Plan Engineering Review
REVIEWER: Elizabeth Leibold
ACTIVITY NUMBER: T07BU01547, T06SA00248, T06CM02975

SUMMARY: The Final Revised Grading Plan was received and reviewed by Engineering. A phone call was made 8SEP10 with the applicant to discuss geotechnical stability of the slopes exceeding max grade recommended by geotechnical engineer. Engineering does not recommend approval of the final grading plan as-built for grading project closure. The following comments need to be addressed:

GRADING PERMIT CLOSURE COMMENTS:
1) DS Sec.11-01.11: Talevera Erosion Control System Report (4AUG10) indicated that portions of the front slope would need to be reconstructed to provide filter fabric beneath the rip rap for slopes steeper than 3:1(H:V). Engineering Inspector will check to see if filter fabric was provided beneath the rip rap. If any slopes indicate missing filter fabric these areas will need to be reconstructed with filter fabric and handplaced rip rap.
2) DS Sec.11-01.16.1: The original geotechnical report indicated that the maximum slope could not exceed 2:1(H:V) and the field report from Talavera described slopes at the site exceeding this grade. These slopes must be either:
a) Reconstructed per the geotechnical report, geotechnical addenda, and approved grading plan, or;
b) A geotechnical addendum would need to be submitted and approved that addresses slope stability for those constructed slopes that exceed 2:1(H:V).
3) Resubmit all documents with geotechnical letter for final review.

If you have questions, you may call me at 837-4934.

Elizabeth Leibold, P.E., CPM, CFM
Civil Engineer
Engineering Division
Planning & Development Services Department
09/17/2010 CPIERCE1 NPPO REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/17/2010 CPIERCE1 OUT TO CUSTOMER Completed