Permit Number: T07BU01462
Parcel: 116300370

Review Status: Completed

Review Details: GRADING

Permit Number - T07BU01462
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2007 ELIZABETH EBERBACH ENGINEERING REVIEW Approved DATE: August 9, 2007
TO: Suzanne Hernandez, Mardonio Talavera PE
SUBJECT: 3156 W Sparkling Starr Grading and Site Plan Review
LOCATION: Wildcat Pass S02-008 lot 37
REVIEWER: Elizabeth Eberbach PE
ACTIVITY NUMBERS: T07BU01462, T07CM02872

Summary: Engineering Division has reviewed the site/grading plan and recommends conditional approval.

GRADING PLAN CONDITIONS OF APPROVAL:
The following conditions must be completed prior to picking up any permits:
1) RETAINING WALL MUST BE REVIEWED AND APPROVED PRIOR TO ISSUANCE OF GRADING PERMIT.
2) FOOT PRINT OF HOUSE ON BUILDING PLANS SHALL MATCH FOOTPRINT ON GRADING PLANS.

GRADING PERMIT CONDITIONS:
The following 10 conditions apply to grading permit T07BU01462:
1) SEPARATE BUILDING PERMIT APPLICATIONS ARE REQUIRED FOR ANY WALLS.
2) CALL FOR PRE-CONSTRUCTION MEETING. FOR A DSD ENGINEERING INSPECTION, CALL IVR (740-6970), OR SCHEDULE WITH A CUSTOMER SERVICE REPRESENTATIVE AT THE DEVELOPMENT SERVICES DEPARTMENT, OR CONTACT DSD ENGINEERING AT 791-5550 EXTENSION 2101, OR SCHEDULE INSPECTIONS ONLINE AT: HTTP://WWW.CI.TUCSON.AZ.US/DSD/ONLINE_SERVICES/ONLINE_PERMITS/ONLINE_PERMITS.HTML
3) A COPY OF THE GRADING PLAN AND GRADING PERMIT SHALL BE KEPT AT THE SITE AT ALL TIMES, UNTIL FINAL GRADING APPROVAL.
4) ANY REVISION TO THE GRADING PLAN MAY REQUIRE A RE-SUBMITTAL OF A REVISED GRADING PLAN FOR REVIEW. CONTACT DSD ENGINEERING AT 791-5550 TO DISCUSS CHANGES IN GRADING DESIGN.
5) IF GRADING CONSTRUCTION IS EXPECTED TO LAST LONGER THAN THE EXPIRATION DATE OF THE GRADING PERMIT, CONTACT DSD TO RENEW/EXTEND THE GRADING PERMIT. IF FINAL GRADING INSPECTION HAS NOT BEEN COMPLETED BEFORE THE GRADING PERMIT EXPIRES, AND THE PERMIT HAS NOT BEEN RENEWED, ADDITIONAL FEES AND REVIEWS MAY BE REQUIRED.
6) THE PERMITEE SHALL NOTIFY THE DSD WHEN THE GRADING OPERATION IS READY FOR FINAL GRADING INSPECTION. FINAL GRADING APPROVAL SHALL NOT BE GIVEN UNTIL ALL WORK, INCLUDING INSTALLATION OF ALL DRAINAGE IMPROVEMENTS AND THEIR PERMANENT PROTECTIVE DEVICES, AND ALL EROSION CONTROL MEASURES HAVE BEEN COMPLETED IN ACCORDANCE WITH THE APPROVED GRADING PLAN AND GRADING PERMIT, AND ALL CONDITIONS OF PERMIT ARE COMPLETED.
7) THERE SHALL BE NO DISTURBANCE OUTSIDE OF THE DISTURBANCE/GRADING LIMITS. A MINIMUM 2-FT SETBACK IS REQUIRED AT ALL PROPERTY LINES.
8) DRIVEWAY SHALL BE CONSTRUCTED TO PROVIDE NO STEEPER THAN A 15% SLOPE.
9) PER HDZ REQUIREMENTS ANY ROCK SHALL BE EITHER HANDPLACED RIP RAP WITH FLITER FABRIC OR HANDPLACED GROUTED RIP RAP.
10) SCALE OF DRAWING IS LABELED AS ¼"=1'-0", HOWEVER PLANVIEW SCALES OUT AT 1-IN = 20-FT.

I can be reached at 837-4934 if you have questions.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Division
Development Services Department


The following 10 conditions apply to grading permit T07BU01462:
1) CALL FOR PRE-CONSTRUCTION MEETING. FOR A DSD ENGINEERING INSPECTION, CALL IVR (740-6970), OR SCHEDULE WITH A CUSTOMER SERVICE REPRESENTATIVE AT THE DEVELOPMENT SERVICES DEPARTMENT, OR CONTACT DSD ENGINEERING AT 791-5550 EXTENSION 2101, OR SCHEDULE INSPECTIONS ONLINE AT: HTTP://WWW.CI.TUCSON.AZ.US/DSD/ONLINE_SERVICES/ONLINE_PERMITS/ONLINE_PERMITS.HTML
2) A COPY OF THE GRADING PLAN AND GRADING PERMIT SHALL BE KEPT AT THE SITE AT ALL TIMES, UNTIL FINAL GRADING APPROVAL.
3) ANY REVISION TO THE GRADING PLAN MAY REQUIRE A RE-SUBMITTAL OF A REVISED GRADING PLAN FOR REVIEW. CONTACT DSD ENGINEERING AT 791-5550 TO DISCUSS CHANGES IN GRADING DESIGN.
4) IF GRADING CONSTRUCTION IS EXPECTED TO LAST LONGER THAN THE EXPIRATION DATE OF THE GRADING PERMIT, CONTACT DSD TO RENEW/EXTEND THE GRADING PERMIT. IF FINAL GRADING INSPECTION HAS NOT BEEN COMPLETED BEFORE THE GRADING PERMIT EXPIRES, AND THE PERMIT HAS NOT BEEN RENEWED, ADDITIONAL FEES AND REVIEWS MAY BE REQUIRED.
5) THE PERMITEE SHALL NOTIFY THE DSD WHEN THE GRADING OPERATION IS READY FOR FINAL GRADING INSPECTION. FINAL GRADING APPROVAL SHALL NOT BE GIVEN UNTIL ALL WORK, INCLUDING INSTALLATION OF ALL DRAINAGE IMPROVEMENTS AND THEIR PERMANENT PROTECTIVE DEVICES, AND ALL EROSION CONTROL MEASURES HAVE BEEN COMPLETED IN ACCORDANCE WITH THE APPROVED GRADING PLAN AND GRADING PERMIT, AND ALL CONDITIONS OF PERMIT ARE COMPLETED.
6) THERE SHALL BE NO DISTURBANCE OUTSIDE OF THE DISTURBANCE/GRADING LIMITS. A MINIMUM 2-FT SETBACK IS REQUIRED AT ALL PROPERTY LINES.
7) DRIVEWAY SHALL BE CONSTRUCTED TO PROVIDE NO STEEPER THAN A 15% SLOPE.
8) PER HDZ REQUIREMENTS ANY ROCK SHALL BE EITHER HANDPLACED RIP RAP WITH FLITER FABRIC OR HANDPLACED GROUTED RIP RAP.
9) SCALE OF DRAWING IS LABELED AS ¼"=1'-0", HOWEVER PLANVIEW SCALES OUT AT 1-IN = 20-FT.
10) ANY ADDITIONAL WALLS NOT SHOWN ON THESE PLANS WILL REQUIRE SEPARATE BUILDING PERMIT APPLICATIONS.
08/09/2007 ELIZABETH EBERBACH ENGINEERING REVIEW Approved Retaining wall ok. - EE
08/21/2007 ANDREW CONNOR NPPO REVIEW Denied Any project that does not have required landscape plans shall have a landscape mitigation plan prepared Including aerial photograph, taken in minimum scale of 1" = 60' Place NPP / landscape mitigation table, and aerial photograph on separate sheet measuring at least 24" x 36" indicating scale with the following information:

§ Limits of all areas to be graded.

§ Location of NUOS area

§ Fencing requirements as specified in Development Standard 2-06.2.2.F.
08/22/2007 DAVID RIVERA ZONING REVIEW Denied 08/20/07

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan at this time until the comments by landscape have been addressed. The landsdape review could affect the placement of the proposed structure.

2. Also please keep in mind that a separate site plan approval for the building permit is required prior to any construction of the structure.

3. Additional comments may be forthcoming based on revisions made to the grading plan.

4. If lot 37 is listed as a barrieir free accessible on the tentative plat, demonstrate how the accessibility is to be provided from the street sidewalk to the front door of the house. Draw and label the accessible path and also label the slopes proposed.
09/27/2007 ELIZABETH EBERBACH ENGINEERING counter review Approved DATE: August 9, 2007
TO: Suzanne Hernandez, Mardonio Talavera PE
SUBJECT: 3156 W Sparkling Starr Grading and Site Plan Review
LOCATION: Wildcat Pass S02-008 lot 37
REVIEWER: Elizabeth Eberbach PE
ACTIVITY NUMBERS: T07BU01462, T07CM02872

Summary: Engineering Division has reviewed the site/grading plan and recommends conditional approval.

GRADING PLAN CONDITIONS OF APPROVAL:
The following conditions must be completed prior to picking up any permits:
1) RETAINING WALL MUST BE REVIEWED AND APPROVED PRIOR TO ISSUANCE OF GRADING PERMIT.
2) FOOT PRINT OF HOUSE ON BUILDING PLANS SHALL MATCH FOOTPRINT ON GRADING PLANS.

GRADING PERMIT CONDITIONS:
The following 10 conditions apply to grading permit T07BU01462:
1) SEPARATE BUILDING PERMIT APPLICATIONS ARE REQUIRED FOR ANY WALLS.
2) CALL FOR PRE-CONSTRUCTION MEETING. FOR A DSD ENGINEERING INSPECTION, CALL IVR (740-6970), OR SCHEDULE WITH A CUSTOMER SERVICE REPRESENTATIVE AT THE DEVELOPMENT SERVICES DEPARTMENT, OR CONTACT DSD ENGINEERING AT 791-5550 EXTENSION 2101, OR SCHEDULE INSPECTIONS ONLINE AT: HTTP://WWW.CI.TUCSON.AZ.US/DSD/ONLINE_SERVICES/ONLINE_PERMITS/ONLINE_PERMITS.HTML
3) A COPY OF THE GRADING PLAN AND GRADING PERMIT SHALL BE KEPT AT THE SITE AT ALL TIMES, UNTIL FINAL GRADING APPROVAL.
4) ANY REVISION TO THE GRADING PLAN MAY REQUIRE A RE-SUBMITTAL OF A REVISED GRADING PLAN FOR REVIEW. CONTACT DSD ENGINEERING AT 791-5550 TO DISCUSS CHANGES IN GRADING DESIGN.
5) IF GRADING CONSTRUCTION IS EXPECTED TO LAST LONGER THAN THE EXPIRATION DATE OF THE GRADING PERMIT, CONTACT DSD TO RENEW/EXTEND THE GRADING PERMIT. IF FINAL GRADING INSPECTION HAS NOT BEEN COMPLETED BEFORE THE GRADING PERMIT EXPIRES, AND THE PERMIT HAS NOT BEEN RENEWED, ADDITIONAL FEES AND REVIEWS MAY BE REQUIRED.
6) THE PERMITEE SHALL NOTIFY THE DSD WHEN THE GRADING OPERATION IS READY FOR FINAL GRADING INSPECTION. FINAL GRADING APPROVAL SHALL NOT BE GIVEN UNTIL ALL WORK, INCLUDING INSTALLATION OF ALL DRAINAGE IMPROVEMENTS AND THEIR PERMANENT PROTECTIVE DEVICES, AND ALL EROSION CONTROL MEASURES HAVE BEEN COMPLETED IN ACCORDANCE WITH THE APPROVED GRADING PLAN AND GRADING PERMIT, AND ALL CONDITIONS OF PERMIT ARE COMPLETED.
7) THERE SHALL BE NO DISTURBANCE OUTSIDE OF THE DISTURBANCE/GRADING LIMITS. A MINIMUM 2-FT SETBACK IS REQUIRED AT ALL PROPERTY LINES.
8) DRIVEWAY SHALL BE CONSTRUCTED TO PROVIDE NO STEEPER THAN A 15% SLOPE.
9) PER HDZ REQUIREMENTS ANY ROCK SHALL BE EITHER HANDPLACED RIP RAP WITH FLITER FABRIC OR HANDPLACED GROUTED RIP RAP.
10) SCALE OF DRAWING IS LABELED AS ¼"=1'-0", HOWEVER PLANVIEW SCALES OUT AT 1-IN = 20-FT.

I can be reached at 837-4934 if you have questions.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Division
Development Services Department


The following 10 conditions apply to grading permit T07BU01462:
1) CALL FOR PRE-CONSTRUCTION MEETING. FOR A DSD ENGINEERING INSPECTION, CALL IVR (740-6970), OR SCHEDULE WITH A CUSTOMER SERVICE REPRESENTATIVE AT THE DEVELOPMENT SERVICES DEPARTMENT, OR CONTACT DSD ENGINEERING AT 791-5550 EXTENSION 2101, OR SCHEDULE INSPECTIONS ONLINE AT: HTTP://WWW.CI.TUCSON.AZ.US/DSD/ONLINE_SERVICES/ONLINE_PERMITS/ONLINE_PERMITS.HTML
2) A COPY OF THE GRADING PLAN AND GRADING PERMIT SHALL BE KEPT AT THE SITE AT ALL TIMES, UNTIL FINAL GRADING APPROVAL.
3) ANY REVISION TO THE GRADING PLAN MAY REQUIRE A RE-SUBMITTAL OF A REVISED GRADING PLAN FOR REVIEW. CONTACT DSD ENGINEERING AT 791-5550 TO DISCUSS CHANGES IN GRADING DESIGN.
4) IF GRADING CONSTRUCTION IS EXPECTED TO LAST LONGER THAN THE EXPIRATION DATE OF THE GRADING PERMIT, CONTACT DSD TO RENEW/EXTEND THE GRADING PERMIT. IF FINAL GRADING INSPECTION HAS NOT BEEN COMPLETED BEFORE THE GRADING PERMIT EXPIRES, AND THE PERMIT HAS NOT BEEN RENEWED, ADDITIONAL FEES AND REVIEWS MAY BE REQUIRED.
5) THE PERMITEE SHALL NOTIFY THE DSD WHEN THE GRADING OPERATION IS READY FOR FINAL GRADING INSPECTION. FINAL GRADING APPROVAL SHALL NOT BE GIVEN UNTIL ALL WORK, INCLUDING INSTALLATION OF ALL DRAINAGE IMPROVEMENTS AND THEIR PERMANENT PROTECTIVE DEVICES, AND ALL EROSION CONTROL MEASURES HAVE BEEN COMPLETED IN ACCORDANCE WITH THE APPROVED GRADING PLAN AND GRADING PERMIT, AND ALL CONDITIONS OF PERMIT ARE COMPLETED.
6) THERE SHALL BE NO DISTURBANCE OUTSIDE OF THE DISTURBANCE/GRADING LIMITS. A MINIMUM 2-FT SETBACK IS REQUIRED AT ALL PROPERTY LINES.
7) DRIVEWAY SHALL BE CONSTRUCTED TO PROVIDE NO STEEPER THAN A 15% SLOPE.
8) PER HDZ REQUIREMENTS ANY ROCK SHALL BE EITHER HANDPLACED RIP RAP WITH FLITER FABRIC OR HANDPLACED GROUTED RIP RAP.
9) SCALE OF DRAWING IS LABELED AS ¼"=1'-0", HOWEVER PLANVIEW SCALES OUT AT 1-IN = 20-FT.
10) ANY ADDITIONAL WALLS NOT SHOWN ON THESE PLANS WILL REQUIRE SEPARATE BUILDING PERMIT APPLICATIONS.
09/27/2007 ELIZABETH EBERBACH ENGINEERING counter review Approved Retaining wall ok. - EE

Final Status

Task End Date Reviewer's Name Type of Review Description
08/23/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
08/23/2007 GERARDO BONILLA REJECT SHELF Completed