Permit Review Detail
Review Status: Completed
Review Details: WALLS SUBMITTAL
Permit Number - T07BU01394
Review Name: WALLS SUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/28/2007 | RBROOKS1 | BUILDING-COMMERCIAL | REVIEW | Denied | 1. REVIEW OF THE WALL AND FOOTING DESIGNS COULD NOT BE COMPLETED DUE TO THE SUBMITTAL OF AN INCOMPLETE SET OF PLANS. pLEASE PROVIDE A COMPLETE SET OF CALCULATIONS VERIFYING THAT THE DERIVATION OF THE WIND PRESSURE IS IN ACCORDANCE WITH ASCE 7-05 SECTION 6.5.14 FOOTING TOP REINFORCEMENT SHOULD BE INSTALLED IN SECTION 3/S5 FOR LOADS ACTING TO THE RIGHT. REFERENCE IBC SECTION 1604.4 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/29/2007 | VFLORES1 | OUT TO CUSTOMER | Completed |