Review Details: RESUBMITTAL - GRADING

Permit Number - T07BU01380
Review Name: RESUBMITTAL - GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/14/2007 PAUL MACHADO ENGINEERING REVIEW Approv-Cond To: Steve Wollerman DATE: December 14, 2007
South Western Consulting Engineers, LLC
435 E. 9th Street
Tucson, Arizona 85705
SUBJECT: 9121 E. Camino Abril Grad lot 23
Grading Plan T07BU01380 (Third Review)
T14S, R15E, Section 27

RESUBMITTAL REQUIRED: SWPPP

The Storm Water Pollution Prevention Plan (SWPPP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:
1. The GP has been accepted by Engineering.
Drainage report:
1. The DR has been accepted by Engineering.

Stormwater pollution prevention plan:
1. The SWPPP certifications must be signed prior to complete approval.
2. The SWPPP is a dynamic document, insert blank pages into the report where any changes in field may be recorded.
3. Insert the SWPPP control (BMP) plan (24"x36") into a folder into the report.
4. The SWPPP has been conditionally approved by Engineering. Re-submit the SWPPP when all comments have been addressed.


If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/9121 E. Camino Abril Grad lot 23_3

Final Status

Task End Date Reviewer's Name Type of Review Description
01/11/2008 SUE REEVES APPROVAL SHELF Completed
01/11/2008 CINDY AGUILAR OUT TO CUSTOMER Completed