Permit Number: T07BU01378
Parcel: 141113840

Review Status: Completed

Review Details: RESUBMITTAL - GRADING

Permit Number - T07BU01378
Review Name: RESUBMITTAL - GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/14/2007 PAUL MACHADO ENGINEERING REVIEW Denied To: Steve Wollerman DATE: December 14, 2007 South Western Consulting Engineers, LLC
435 E. 9th Street
Tucson, Arizona 85705
SUBJECT: 9089 E. Camino Abril Grad lot 21
Grading Plan T07BU01378 (Third Review)
T14S, R15E, Section 27

RESUBMITTAL REQUIRED: Grading Plan.

The Grading Plan (GP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:
1. Please include a response letter to the comments along with the corrected copies of the GP.
2. The fill slopes shown on the plan cannot be located outside the project boundary limits (property line) without a slope easement. Revise as required.
3. Revise the cut and fill quantities.

Drainage report:
1. The DR has been accepted by Engineering. Re-submit the DR along with the corrected copies of the Grading Plan.

Stormwater pollution prevention plan:
1. The SWPPP certifications must be signed prior to complete approval.
2. The SWPPP is a dynamic document, insert blank pages into the report where any changes in field may be recorded.
3. Insert the SWPPP control (BMP) plan (24"x36") into a folder into the report.
4. The SWPPP has been conditionally approved by Engineering. Re-submit the SWPPP along with the corrected copies of the Grading Plan.

If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/9089 E. Camino Abril Grad lot 21_3

Final Status

Task End Date Reviewer's Name Type of Review Description
12/14/2007 CINDY AGUILAR OUT TO CUSTOMER Completed