Permit Number: T07BU01377
Parcel: 141113920

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T07BU01377
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2007 ANDREW CONNOR NPPO REVIEW Approved
11/06/2007 DAVID RIVERA ZONING REVIEW Approved
12/10/2007 PAUL MACHADO ENGINEERING REVIEW Denied To: Steve Wollerman DATE: December 11, 2007
South Western Consulting Engineers, LLC
435 E. 9th Street
Tucson, Arizona 85705
SUBJECT: 9082 E. Camino Abril, Lot 29
Grading Plan T07BU01377 (Second Review)
T14S, R15E, Section 27

RESUBMITTAL REQUIRED: Grading Plan, Drainage Report and SWPPP

The Grading Plan (GP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:
1. Please include a response letter to the comments along with the corrected copies of the GP.
2. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0. The position of the refuse enclosure indicates that the service vehicle will have to reverse in excess of 120 feet to exit the property. This is three times the distance allowed of 40' maximum reverse distance. Revise as required.
3. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0. The refuse enclosure is properly dimensioned, however, access to the dumpter does not meet COT standard. See comment no. 2.
4. An hourly review fee for the third grading plan submittal and review may be accessed depending on the correctness of the revisions. All third submittals will charged an hourly review rate of $75.00 per City of Tucson Development Services Department.

Drainage report:
1. The DR has been accepted by Engineering. Re-submit the DR along with the corrected copies of the Grading Plan.

Stormwater pollution prevention plan:
1. The SWPPP has been accepted by Engineering. Re-submit the SWPPP along with the corrected copies of the Grading Plan.


If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/9082 E. Camino Abril Grad lot 29_2

Final Status

Task End Date Reviewer's Name Type of Review Description
12/14/2007 SUE REEVES OUT TO CUSTOMER Completed
12/14/2007 SUE REEVES REJECT SHELF Completed