Permit Number: T07BU01283
Parcel: 10712231B

Address:
2820 N CASTRO AV

Review Status: Active

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T07BU01283
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2008 ANDREW CONNOR NPPO REVIEW Approved
02/14/2008 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: February 13, 2008
SUBJECT: Grading Plan
TO: MPE
LOCATION: 2820 N Castro Ave, T13S, R13E, Section 36, Ward 3
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T07BU01283 (First Review)


RESUBMITTAL REQUIRED: Grading Plan

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed grading plan for the above referenced property. Engineering Division does not recommend approval of the grading plan at this time. Please address the following review comments prior to the next submittal.

Provide a response letter to the comments along with the corrected copies of the site plan.

Grading Plan:
1. Add note: "Depress all landscaped areas a maximum of 6" for water harvesting"
2. Add the following notes to the grading plan notes:
ยท "The approved Grading Plan is the only acceptable construction plan onsite. The Contractor may not use any other plans, such as the approved Tentative Plat and/or Development Plan, for construction purposes. The Contractor may ask the Development Services Inspector to consult with the other approved plans for additional information or details that might not be included on the approved grading plan but needed for completion of work."

3. Provide the grading plan number in the lower right corner of each sheet that pertains to the grading. In this case both site and grading information is provided within the multiple sheets. Include site plan number at the lower right hand corner of the sheet as well.
4. Provide legend and show all symbols in the legend for C1.1.
5. List all Cut and Fill quantities in cubic yards on grading sheet.
6. Show cross section with transverse and longitudinal slopes. Provide label for the rip rap cross section - call out on plan accordingly.
7. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
8. Call out all slopes and stabilization material (concrete, riprap, gabbions or vegetation).
9. Cut or fill slopes require a 2' minimum setback from property line.

10. Flow arrows, grades and flow rates within and adjacent to site to show drainage scheme.
11. Call out peak discharges entering and exiting the site.
12. Revise trash enclosure to meet minimum standard requirements. See attached detail for specific detail information.
13. Additional comments may be forthcoming.


If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov
Bianca Ramirez, CFM
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax
02/25/2008 MICHAEL ST. PAUL ZONING REVIEW Denied February 25, 2008

Development Services Department
Zoning Review Section

Michael St.Paul
Planning Technician

T07BU01283 Grading Plans for T07CM02414
2820 North Castro Avenue

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering Section and until all zoning comments or concerns have been addressed.

2. The grading plan appears to match the approved site plan. Please submit two copies of the last approved and stamped Site Plan, Landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the approved development plan. Additional comments may be forthcoming.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/26/2008 SHANAE POWELL REJECT SHELF RECEIVED